Refrigerating Specialties Division

1

BULLETIN 23-07B

Type A4AO, A4AOE, A4AOS, A4AOSE

August 2006

Installation, Service and Parts Information

ADAPTOMODE

®

 OUTLET

PRESSURE REGULATORS

Types:   A4AO, A4AOE, A4AOS and

 

A4AOSE

Port Size 20 - 100 mm (3/4” - 4”)

FOR AMMONIA, R-12, R-22, R-502
OTHER REFRIGERANTS AND OIL

FEATURES

•  Pilot operated characterized Modulating Plug 

precise control

•  Suitable for all common refrigerants and oil

•  27.6 bar (400 psig) design pressure (MRP)

•  Flanges for threaded or welded steel pipe and 

copper tube (copper not for ammonia)

•  Interchangeable parts

•  Easy to service

•  Close coupled strainers, optional

•  Many control variations are possible with the 

use of a few Modules and kits. (See Adaptomode 

Pressure Regulator Bul. 23-06)

•  Stainless Steel Diaphragm

•  Chrome Plated Pilot Seat

•  Manual Opening Stem

Description

These compact, heavy duty, pilot operated, iron alloy (ASTM A126 Class 

B) Outlet Pressure regulators are suitable for Ammonia, R-12, R-22, 

R-502 and other common refrigerants and fl uids approved for use in 

refrigerant valves. All A4 Regulators are pilot operated using upstream 

Purpose

Modulates fl ow of refrigerant gas or liquid to maintain a constant down-

stream pressure as set-for, despite fl uctuations in load. The regulator 

will gradually close when downstream pressure begins to rise above the 

setting and will gradually open when pressure begins to fall below the 

setting. The regulator cannot maintain set-for pressure if uncontrolled 

branch pipe lines feed into the main pipeline downstream of the A4AO 

Regulator. Typical uses are as follows:

Protect Compressor Motor from Overload (Hold-back): 

See capacity 

ratings in Condensed Catalog CC-11. Select at design parameters i.e., 

tons, evaporator temp./press and pressure drop.

Hot  Gas  Bypass  Capacity  Control: 

See  Bulletin  BYG-4,  Condensed 

Catalog CC-11.

Limit Refrigerant Pressure in a Liquid Line: 

Contact factory for selec-

tion assistance.

Prevent Deep Vacuum in Booster Suction: 

See capacity ratings Con-

densed Catalog CC-11 “Compressor Suction Loading”. For selections 

other than those shown, contact factory.

Prevent Pressure Rise in Suction Main: 

Select valve based on mass fl ow 

requirements. Valve Cv and pressure drop across regulator. Contact 

factory for proper selection assistance, if required.

Hot  Gas  Defrost  Control: 

Refer  to  Condensed  Catalog  CC-1  1  and 

Bulletin 90-10 for ratings and application information.

pressure for the opening force and requires a minimum 0.14 bar (2 psig) 

pressure drop to fully open.
These  valves  are  generally  ordered  with  close  coupled  strainer  to 

prevent entrance of foreign material into the valve and the rest of the 

system. (See current Bulletin 00-10 for strainer information.)
The fl uid temperature range for the A4 Series of Regulators is -45°C 

to 105°C (-50°F to 220°F).

050321

PILOT PLUG

I S O   9 0 0 0 - 2 0 0 0  C E R T I F I E D

Содержание ADAPTOMODE A4AO

Страница 1: ...g and will gradually open when pressure begins to fall below the setting The regulator cannot maintain set for pressure if uncontrolled branch pipe lines feed into the main pipeline downstream of the...

Страница 2: ...odudapter Fig 2 item 28A is used only with the A4AOS The Pilot Solenoid is mounted on Pad 1 of the Modudapter along with Moduplate item 52 mounted on Pad 2 with S showing to the outside of the regulat...

Страница 3: ...s are cold since moisture can condense on parts and cause rapid rusting When replacing gaskets they should be oiled very lightly with refrigerant oil before assembly Install bottom cap assembly rst an...

Страница 4: ...ead Safety Bulletin RSB Dirt in the system is the greatest single cause of regulator malfunction All screens or lters must be cleaned or replaced when they become dirty At start up it is especially im...

Страница 5: ...or does not shut off ow Diaphragm or seat dirty damaged or frozen Clean or replace Clean strainer Diaphragm follower stuck or damaged Clean or replace Install follower carefully Piston jammed with exc...

Страница 6: ...1 1 200771 1 19 Gasket Only Avail with Kit 1 Only Avail with Kit 1 22 Nut Retainer Only Avail with Kit 1 Only Avail with Kit 1 23 Spring Only Avail with Kit 1 Only Avail with Kit 1 24 Plug Pilot Only...

Страница 7: ...Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 22 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit...

Страница 8: ...Cap Kit 202110 1 202110 1 33 38 40 44 Full Cap Bottom Assembly Kit 202010 1 202011 1 33 38 40 44 50 Cap Bottom Assembly Kit 202347 1 1 33 38 40 44 17 Cap Bottom Assembly Kit 202346 1 1 3 6 12 19 Full...

Страница 9: ...y Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 43 44 202110 1 202110 1 202110 1 202110 1 202110 1 202110 1 33 38 40 44 202012 1 202013 1 202014 1 202015 1 202016...

Страница 10: ...4 4 Fig 4 Item Description Qty Kit Number 55 Screw 1 Only Avail with Kit 58 Coil Assemly 1 See Page 8 67 O Ring 1 Only Avail with Kit 68 Knob 1 Only Avail with Kit 67 68 Knob Kit 1 205047 69 Lens 1 On...

Страница 11: ...18 6 525 20 7 538 21 2 657 25 9 710 28 4 B 148 5 8 162 6 3 177 6 9 181 7 1 273 10 7 292 11 5 C 177 6 7 216 8 5 264 10 4 264 10 4 324 12 7 352 14 6 D 1 2 229 9 0 1 1 4 269 10 6 FPT FOR 3 4 229 9 0 1 1...

Страница 12: ...certain precautions be taken to avoid damage which could result from liquid expansion Temperature increase in a piping section full of solid liquid will cause high pressure due to the expanding liquid...

Отзывы: