Refrigerating Specialties Division

5

A4AO OUTLET REGULATOR

OPERATION

The outlet pressure is sensed under the
diaphragm through the sensing tube, which is part
of the Flange Ring-tube assembly. When the force
created by the outlet pressure acting under the
diaphragm is less than the force of the range
spring, the pilot is open, allowing pressure to enter
on top of the piston. This causes the power piston
to force the throttling plug to open to maintain
constant outlet pressure. Decrease in the outlet
pressure allows the range spring to open the pilot
further, allowing more pressure on top of the piston
and opening the throttling plug further. An increase
in the outlet pressure will lift the diaphragm against
the force of the range spring, allowing the pilot
plug to start closing. The pressure on top of the

power piston is decreased and the closing spring acts to reduce the opening
of the throttling plug and the flow of fluid through the regulator. The pressure
on top of the power piston is controlled by the flow through the pilot seat
and the bleed through a bleed hole in the power piston and through the
clearance between the piston and the cylinder. A maximum of 0.14 bar
(2 psi) pressure drop across the regulator is required to open it fully.

ADJUSTMENT

Install a pressure gauge at the regulator gauge port in the A4AO Adapter
next to the sensing tube. Back the adjusting stem all the way out to stop
(counter-clockwise). This will reduce the set-point to its lowest level and
cause the valve to close. Operate the system until the outlet pressure is
lower than desired. Slowly turn in the adjusting stem (clockwise) until the
desired outlet pressure is reached.

A4AO OUTLET PRESSURE SETTING RANGES

Set Point Ranges

Approx. Pressure Change

per Turn of Adjusting Screw

V: 500 mm hg to 8 bar

1.8 bar

 

(25 psi)

(20 in Hg to 120 psig)

D: 5 to 20 bar

 

(75 to 280 psig)

3.7 bar (53 psi)

A4AOE OUTLET PRESSURE REGULATOR,
REMOTE SENSING CONNECTION

This regulator allows control of downstream pressure at a point remote
from the outlet of the regulator. The pressure from the desired sensing
point is connected directly to the A4AOE adapter at Fitting 7A in place of
the Flange Ring-tube Assembly 20 shown for the A4AO. Thus the regulator
will control the pressure at the sensing point. The regulator operation and
adjustment is the same as for A4AO.

A4AOS OUTLET PRESSURE REGULATOR
WITH ELECTRIC SHUT-OFF

The A4AOS Pressure Regulator controls outlet
pressure when the modular solenoid pilot is
energized, and closes when the solenoid pilot
is de-energized regardless of the pressure
setting or pressure in the regulator. The
Modudapter® (Fig. 5) is used for this regulator.
The pilot  solenoid valve is mounted in the
location shown for A4AS on page 7.

Adjustment - With the solenoid energized,
proceed as with the A4AO.

A4AOT REVERSE ACTING
TEMPERATURE REGULATOR

The A4AOT Regulator modulates flow in
response to the temperature variations sensed
by its thermal bulb. A special temperature pilot
replaces the standard A4AO pilot. A drop in
temperature will cause the valve to open; a rise
will cause it to close. This valve responds only
to temperature changes and is not a pressure
regulator.

Operation  - Temperature change of the
controlled medium is sensed by the thermal bulb

of the pilot. As the bulb is warmed, the charge in the thermal element
expands. The resulting force is transmitted to the pilot plug by a push rod,
causing the pilot to close. This in turn causes the main valve to close. A
drop in the temperature at the thermal bulb causes the opposite to happen,
thus allowing the main valve to open. Standard range is -30°C to +30°C
(-20°F to 80°F). Also available 20°C to 60°C (60°F to 140°F). Maximum
temperature to which thermal bulb can be exposed is 65°C (150°F).

The A4AOTS Regulator combines the Reverse Acting Temperature
Regulator with Electric Shut-Off. It operates the same as the A4AOT when
the solenoid pilot is energized, and closes when the solenoid pilot is
de-energized regardless of the temperature setting or pressure in the
regulator.

A4AOM ELECTRICALLY COMPENSATED
OUTLET PRESSURE REGULATOR

This pressure regulator modulates the outlet pressure in accordance to
load requirements as sensed by an electric thermostat or humidistat which
varies an electric signal applied to a motor mounted on the regulator pilot.
The motor operation is as described on Page 9 for A4AM, except the A4AOM
operates as an outlet pressure regulator. Available in standard Range V or
Range D.

The A4AOMS Regulator combines the Electrically Compensated Outlet
Pressure Regulator with the Modular Solenoid Pilot to provide Electric
Shut-off (see Page 7 for electric shut-off operation). It operates the same
as the A4AOM when the solenoid pilot is energized and closes when the
solenoid is de-energized regardless of the pressure setting or the pressure
in the regulator.

Содержание ADAPTOMODE A4A Series

Страница 1: ...loose particles should be removed from the flange interior before the regulator is installed between the flanges It is advisable to install a close coupled companion strainer RSF at the inlet of the...

Страница 2: ...the way in until the flats on the stem barely protrude from the stuffing box nut Push Piston 30 down against the spring force The piston should move freely down and be returned by the spring force If...

Страница 3: ...1 1000 20 1 81 1000 20 1 44 Seal Cap 20 4005 00 1 20 4005 00 1 20 4005 00 1 20 4005 00 1 20 4005 00 1 20 4005 00 1 20 1130 00 1 20 1130 00 1 45 Gasket Flange 81 1000 03 2 81 1000 03 2 81 1000 04 2 81...

Страница 4: ...essure from the desired control point upstream of the regulator is connected to the gauge port leading to under the diaphragm Thus the regulator will control the pressure at this point The regulator o...

Страница 5: ...same as for A4AO A4AOS OUTLET PRESSURE REGULATOR WITH ELECTRIC SHUT OFF The A4AOS Pressure Regulator controls outlet pressure when the modular solenoid pilot is energized and closes when the solenoid...

Страница 6: ...low the disassembly and assembly procedure for the A4A pilot pages 2 and 3 When mounting the pilot place the O Rings 50 into the proper grooves and tighten the Cap Screws 49 evenly The ideal tightenin...

Страница 7: ...the flow or stop the flow through the flow paths in the Modudapter When mounted on Pad 2 with the S side out it blocks flow from Path X to Path Z see Fig 13 and 14 A4AS When mounted on Pad 1 with the...

Страница 8: ...r controls at the higher pressure setting The S6A Modular Solenoid Pilot Fig 12 is mounted on Pad 1 of the Modudapter the A2D Modular Pressure Pilot Fig 10 is mounted on Pad 2 The 20 to 32 mm 3 4 to 1...

Страница 9: ...re exists or in low temperature applications where ice could accumulate on the valve stem the A4AMR with remote pilot can be used The cover should be kept on the motor at all times to protect it from...

Страница 10: ...Screw 90 1000 61 1 83 Mounting Post Honeywell 20 1174 00 4 Mounting Post Penn 20 1174 01 4 84 Guide Post 20 4037 00 1 85 Guide Post Locknut 20 4038 00 1 86 Mounting Plate 20 4093 00 87 Actuating Stem...

Страница 11: ...olenoid valve Types S4 S5 S6N S7 S8 and S9 SYMPTOM PROBABLE REASON CORRECTION Regulator does not Diaphragm or seat dirty damaged Clean or replace Clean strainer shut off flow or frozen Diaphragm follo...

Страница 12: ...pe or valve All hand valves in such locations should be marked warning against accidental closing and must not be closed until the liquid is removed Check valves must never be installed upstream of so...

Отзывы: