D-163
Programming
AC890PX AC Drive
STABILISATION
SETUP::MOTOR CONTROL::STABILISATION
Designed for VOLTS/Hz motor Control Mode.
Enabling this function reduces the problem of unstable running in induction motors. This can be experienced at approximately
half full speed, and under low load conditions.
Parameter Descriptions
ENABLE
PREF: 25.01
Default: TRUE
Range: FALSE / TRUE