D-139
Programming
AC890PX AC Drive
SEQUENCING LOGIC
SETUP::SEQ & REF::SEQUENCING LOGIC
This function block contains all the parameters relating to the sequencing (start and stop) of the Drive.
Before the Drive will respond to the RUN FORWARD, RUN REVERSE or JOG parameters (cause the Drive to run or jog),
the parameters DRIVE ENABLE, NOT FAST STOP and NOT COAST STOP need to be set to TRUE. In addition, the Drive
needs to be healthy (HEALTHY is TRUE). The Drive will only respond to RUN FORWARD, RUN REVERSE and JOG if the
Drive is in the Remote Sequencing mode.
If RUN FORWARD and RUN REVERSE are TRUE, both are ignored and the Drive will stop.
Parameter Descriptions
START DELAY
PREF: 92.25
Default: 0.000 s
Range: 0.000 to 30.000s
Delays the action of "ramping to setpoint" from the Run command. This can allow a period for motor flux to establish before
the ramp to setpoint.
RUN FORWARD
PREF: 92.01
Default: FALSE
Range: FALSE / TRUE
Setting this parameter to TRUE causes the Drive to run in the forward direction.
RUN REVERSE
PREF: 92.02
Default: FALSE
Range: FALSE / TRUE
Setting this parameter to TRUE causes the Drive to run in the reverse direction.
NOT STOP
PREF: 92.03
Default: FALSE
Range: FALSE / TRUE
Setting this parameter TRUE will latch the RUN FORWARD or RUN REVERSE commands. Once latched, they can be reset
to FALSE and the Drive will continue to run. Setting NOT STOP to FALSE causes the run commands to be unlatched.
JOG
PREF: 92.04
Default: FALSE
Range: FALSE / TRUE
Setting this parameter TRUE causes the Drive to run at the speed set by JOG SETPOINT (refer to the REFERENCE JOG
function block). Once jogging, setting JOG to FALSE causes the Drive to ramp to zero.
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...