D-14
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
AUTOTUNE
SETUP::MOTOR CONTROL::AUTOTUNE
Designed for SENSORLESS VEC and CLOSED-LOOP VEC Motor Control Modes.
The autotune is an automatic test sequence performed by the Drive to identify motor model parameters. The motor model is
used by the Sensorless Vector and Closed-Loop Vector control modes. You
MUST
perform an autotune before operating the
Drive in either of the Vector control modes.
Refer to the Chapter 4/5: The Autotune Feature.
Parameter Descriptions
ENABLE
PREF: 80.01
Default: FALSE
Range: FALSE / TRUE
Determines whether the Autotune sequence is operational or not. The Autotune sequence is operational when set to TRUE and
the Drive is run. Refer to Chapter 4/5: The Autotune Feature.
MODE
PREF: 80.02
Default: ROTATING
Range: See below
Selects the Autotune operating mode. Refer to Chapter 4/5: - The Autotune Feature.
Enumerated Value
:
Mode
0 : STATIONARY
determine motor parameters
1 : ROTATING
determine motor parameters
2 : SPD LOOP ROTATING
determine speed loop tuning dependent on motor inertia
3 : SPD LOOP STATIONARY
determine speed loop tuning dependent on motor inertia