![Parker AC30V Series Скачать руководство пользователя страница 180](http://html1.mh-extra.com/html/parker/ac30v-series/ac30v-series_product-manual_3783728180.webp)
A-3
Modbus TCP
AC30V series Variable Speed Drive
FIXED PARAMETER MAPPING - STRINGS
Strings parameters have a parameter number that represents the whole string. This parameter number is mapped to two registers so limits
access to the first four characters. Additional contiguous parameter numbers are set aside so that the whole string can be accessed: one
additional parameter number for each four characters. The strings are packed into the registers
low byte first
.
String Example
A string parameter called
My String
has a string length of 12 characters (plus the null terminator). This will have one parameter number allocated
for the whole string (in this example 161) and 3 further parameter numbers for the string fragments (162-164).
If the value of the string is “0123456789AB”:
Parameter
Number
Represents
Register
Number
Register Value
hi-byte
lo-byte
0161
whole string
“0123456789AB”
00849
‘1’
‘0’
00850
‘3’
‘2’
0162
Fragment
“0123”
00851
‘1’
‘0’
00852
‘3’
‘2’
0163
fragment
“4567”
00853
‘5’
‘4’
00854
‘7’
‘6’
0164
fragment
“89AB”
00855
‘9’
‘8’
00856
‘B’
‘A’
Note: This is example is not a real parameter.
As each AC30V parameter maps to two registers, if the registers that represent the whole string are accessed then only the first four characters
will appear. To access the whole string over Modbus use the registers that map to the parameter number of the whole array plus one, in this
example
0162
(register
00851
). A multiple read or write of registers will then provide access to the whole string.
Содержание AC30V Series
Страница 140: ...9 24 Setup Wizard AC30V series Variable Speed Drive MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 141: ...Setup Wizard 9 25 AC30V series Variable Speed Drive Figure 9 16 Charting Drive Parameters...
Страница 205: ...Compliance C 10 AC30V series Variable Speed Drive Frame H Frame J Frame K contact Parker for more information...
Страница 341: ...Parameter Reference D 102 AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...