D-110
Parameter Reference
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units
WQ
View
Notes MBus
0420
Actual Pos Torque Lim
Advanced Monitor::Motor and Drive
Parameters::Motor Control::Torque Limit
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01367
0421
Actual Neg Torque Lim
Same as PNO 420
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01369
0422
VHz Shape
Advanced Setup::Motor Control::Control and Type
Parameters::Motor Control::Fluxing VHz
USINT
(enum)
0
0:LINEAR LAW
1:FAN LAW
2:USER DEFINED
STOPPED TECHNICIAN 4
01371
0423
VHz User Freq
Parameters::Motor Control::Fluxing VHz
ARRAY[0..10]
STOPPED ENGINEER
01373
0424
VHz User Freq[0]
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01375
0425
VHz User Freq[1]
Parameters::Motor Control::Fluxing VHz
REAL
10.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01377
0426
VHz User Freq[2]
Parameters::Motor Control::Fluxing VHz
REAL
20.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01379
0427
VHz User Freq[3]
Parameters::Motor Control::Fluxing VHz
REAL
30.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01381
0428
VHz User Freq[4]
Parameters::Motor Control::Fluxing VHz
REAL
40.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01383
0429
VHz User Freq[5]
Parameters::Motor Control::Fluxing VHz
REAL
50.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01385
0430
VHz User Freq[6]
Parameters::Motor Control::Fluxing VHz
REAL
60.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01387
0431
VHz User Freq[7]
Parameters::Motor Control::Fluxing VHz
REAL
70.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01389
0432
VHz User Freq[8]
Parameters::Motor Control::Fluxing VHz
REAL
80.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01391
0433
VHz User Freq[9]
Parameters::Motor Control::Fluxing VHz
REAL
90.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01393
0434
VHz User Freq[10]
Parameters::Motor Control::Fluxing VHz
REAL
100.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01395
0435
VHz User Volts
Parameters::Motor Control::Fluxing VHz
ARRAY[0..10]
STOPPED ENGINEER
01397
0436
VHz User Volts[0]
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01399
0437
VHz User Volts[1]
Parameters::Motor Control::Fluxing VHz
REAL
10.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01401
0438
VHz User Volts[2]
Parameters::Motor Control::Fluxing VHz
REAL
20.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01403
0439
VHz User Volts[3]
Parameters::Motor Control::Fluxing VHz
REAL
30.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01405
0440
VHz User Volts[4]
Parameters::Motor Control::Fluxing VHz
REAL
40.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01407
0441
VHz User Volts[5]
Parameters::Motor Control::Fluxing VHz
REAL
50.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01409
0442
VHz User Volts[6]
Parameters::Motor Control::Fluxing VHz
REAL
60.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01411
0443
VHz User Volts[7]
Parameters::Motor Control::Fluxing VHz
REAL
70.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01413
0444
VHz User Volts[8]
Parameters::Motor Control::Fluxing VHz
REAL
80.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01415
0445
VHz User Volts[9]
Parameters::Motor Control::Fluxing VHz
REAL
90.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01417
0446
VHz User Volts[10]
Parameters::Motor Control::Fluxing VHz
REAL
100.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01419
0447
Fixed Boost
Same as PNO 422
REAL
0.0
0.0 to 5.0
%
ALWAYS
TECHNICIAN 4
01421
0448
Auto Boost
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN 4
01423
0450
Acceleration Boost
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN 4
01427
0451
Energy Saving Enable
Parameters::Motor Control::Fluxing VHz
BOOL
FALSE
ALWAYS
TECHNICIAN 4
01429
0455
Rated Motor Current
Advanced Setup::Motor Control::Motor Nameplate
Parameters::Motor Control::Motor Nameplate
REAL
1.00
0.00 to 10000.00
A
STOPPED TECHNICIAN 4
01437
0456
Base Voltage
Same as PNO 455
REAL
400.00
0.00 to 1000.00
V
STOPPED TECHNICIAN 4
01439
0457
Base Frequency
Same as PNO 455
REAL
50.00
0.00 to 1000.00
Hz
STOPPED TECHNICIAN 4
01441
0458
Motor Poles
Same as PNO 455
INT
4,
2 to 1000
STOPPED TECHNICIAN 4
01443
0459
Nameplate Speed
Same as PNO 455
REAL
1420.00
0.00 to 30000.00
RPM STOPPED TECHNICIAN 4
01445
0460
Motor Power
Same as PNO 455
REAL
2.20
0.00 to 3000.00
kW
STOPPED TECHNICIAN 4
01447
0461
Power Factor
Same as PNO 455
REAL
0.79
0.00 to 1.00
STOPPED TECHNICIAN 4
01449
0464
100% Speed in RPM
Advanced Setup::Motor Control::Control and Type
Parameters::Motor Control::Scale Setpoint
REAL
1500.0
0.0 to 20000.0
RPM ALWAYS
TECHNICIAN
01455
0467
PMAC SVC Auto Values
Parameters::Motor Control::PMAC SVC
BOOL
TRUE
ALWAYS
TECHNICIAN 4
01461
0468
PMAC SVC LPF Speed Hz
Parameters::Motor Control::PMAC SVC
REAL
60.00
0.00 to 10000.00
Hz
ALWAYS
TECHNICIAN 4
01463
0469
PMAC SVC P Gain
Parameters::Motor Control::PMAC SVC
REAL
1.00
0.00 to 10000.00
ALWAYS
TECHNICIAN 4
01465
0470
PMAC SVC I Gain Hz
Parameters::Motor Control::PMAC SVC
REAL
20.00
0.00 to 10000.00
Hz
ALWAYS
TECHNICIAN 4
01467
0476
PMAC SVC Open Loop Strt
Parameters::Motor Control::PMAC SVC
BOOL
TRUE
ALWAYS
TECHNICIAN 4
01479
0477
PMAC SVC Start Time
Parameters::Motor Control::PMAC SVC
TIME
0.500
0.000 to 1000.000
s
ALWAYS
TECHNICIAN 4
01481
0478
PMAC SVC Start Cur
Parameters::Motor Control::PMAC SVC
REAL
10.0
0.0 to 200.0
%
ALWAYS
TECHNICIAN 4
01483
0479
PMAC SVC Start Speed
Parameters::Motor Control::PMAC SVC
REAL
5
0 to 200
%
ALWAYS
TECHNICIAN 4
01485
0484
Seq Stop Method VHz
Advanced Setup::Motor Control::Control and Type
Parameters::Motor Control::Ramp
USINT
(enum)
1
0:DISABLED VOLTAGE
1:RAMP
2:STOP RAMP
3:DC INJECTION
ALWAYS
TECHNICIAN 4
01495
Содержание AC30V Series
Страница 33: ...4 15 Installation AC30V series Variable Speed Drive Wiring Diagrams APPLICATION 0 BASIC SPEED CONTROL...
Страница 34: ...Installation 4 16 AC30V series Variable Speed Drive Basic Speed Control Wiring...
Страница 35: ...4 17 Installation AC30V series Variable Speed Drive APPLICATION 1 AUTO MANUAL CONTROL...
Страница 36: ...Installation 4 18 AC30V series Variable Speed Drive Auto Manual Control Wiring...
Страница 37: ...4 19 Installation AC30V series Variable Speed Drive APPLICATION 2 RAISE LOWER TRIM...
Страница 38: ...Installation 4 20 AC30V series Variable Speed Drive Raise Lower Trim Wiring...
Страница 39: ...4 21 Installation AC30V series Variable Speed Drive APPLICATION 3 PRESETS SPEEDS...
Страница 40: ...Installation 4 22 AC30V series Variable Speed Drive Presets Speeds Wiring...
Страница 41: ...4 23 Installation AC30V series Variable Speed Drive APPLICATION 4 PID CONTROL...
Страница 42: ...Installation 4 24 AC30V series Variable Speed Drive PID Control Wiring...
Страница 162: ...Sequencing Logic B 2 AC30V series Variable Speed Drive SEQUENCING DIAGRAM...
Страница 174: ...Compliance C 8 AC30V series Variable Speed Drive Conducted Emissions Profile Unfiltered Product Frame D Frame E Frame F...
Страница 277: ...D 80 Parameter Reference AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...
Страница 325: ...E 2 E Plan Library AC30V series Variable Speed Drive Which then brings up the E Plan page...