Programming
Page
D-62
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
PLS (Programmable Limit Switch)
SETUP::MOTION::PLS
Designed for BRUSHLESS SERVO Motor Control Mode.
The
PLS block is designed to activate an output when a variable is in a predefined range.
Parameter Descriptions
ENABLE
PREF: 153.01, 154.01
Default: FALSE
Range: FALSE / TRUE
Set this parameter to TRUE to enable the block.
SOURCE
PREF: 153.02, 154.02
Default: 0
Range: See below
This parameter selects the variable that will be monitored.
Enumerated Value
:
State
0 : POS ACTUAL
The block will monitor the actual position.
1 : SPEED ACTUAL
The block will monitor the actual speed.
2 : TRACKING ERROR
The block will monitor the tracking error.
3 : POS TH
The block will monitor the theorytical position
4 : SPEED TH
The block will monitor the theorytical speed
5 : ACCEL TH
The block will monitor the theorytical acceleration
HIGH
PREF: 153.03, 154.03
Default: 0
Range: INT MIN to INT MAX
This parameter sets the range’s upper limit.
LOW
PREF: 153.04, 154.04
Default: 0
Range: INT MIN to INT MAX
This parameter sets the range’s lower limit. If LOW is larger than HIGH then the output will always be active.