Trips and Fault Finding
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
10-3
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Resetting a Trip Condition
Before a trip can be reset, the trip condition must be removed.
Note
A Heatsink Over-temperature trip may not reset immediately. The unit needs to cool sufficiently.
Local Mode
To reset a trip in Local Mode:
Remove the trip condition
Press the Stop key to clear the trip. You can now press Run to
restart the system..
Remote Mode
To reset a trip in Remote Mode:
Remove the trip condition
Press the Stop key to clear the trip. You can now press Run to
restart the system..
Remove the trip condition
-
Alternatively, remove and re-apply the 24V supply at X01, or
toggle the ENABLE to 0V and then 24V to restart the system.