24
8903/RS RS485 Communications Interface
Communications Status
The COMMS STATUS parameter (PREF 95.08, Modbus Holding Register 7097) in the
COMMS CONTROL function block monitors the sequencing of the Drive. It is a 16-bit word
based on standard fieldbus drive profiles. Some bits are not implemented in the initial release
and are set to 0 (see “Supported” column of the table below).
Bit
Name
Description
Supported
0
Ready To Switch On
9
1
Switched On
Ready for operation (refer control bit 0)
9
2
Operation Enabled
(refer control bit 3)
9
3 Fault
Tripped
9
4
(Not) Voltage Disabled OFF 2 Command pending
9
5
(Not) Quick Stop
OFF 3 Command pending
9
6
Switch On Disable
Switch On Inhibited
9
7 Warning
8
SP / PV in Range
9
Remote
= 1 if Drive will accept Command Word
9
10 Setpoint
Reached
= 1 if not ramping
9
11
Internal Limit Active
= 1 if current limit active or speed loop is
in torque limit
9
12
13
14
15
Ready To Switch On
Same as the SWITCH ON ENABLE output parameter of the SEQUENCING LOGIC function
block.
Switched On
Same as the SWITCHED ON output parameter of the SEQUENCING LOGIC function block.
Operation Enabled
Same as the RUNNING output parameter of the SEQUENCING LOGIC function block.
Fault
Same as the TRIPPED output parameter of the SEQUENCING LOGIC function block.
(Not) Voltage Disabled
If in Remote Comms mode, this is the same as Bit 1 of the COMMS COMMAND parameter.
Otherwise it is the same as the NOT COAST STOP input parameter of the SEQUENCING
LOGIC function block.
(Not) Quick Stop
If in Remote Comms mode, this is the same as Bit 2 of the COMMS COMMAND parameter.
Otherwise it is the same as the NOT FAST STOP input parameter of the SEQUENCING
LOGIC function block.
Switch On Disable
Set (=1) only when in START DISABLED state.
Remote
This bit is set (= 1) if the Drive is in Remote mode
AND
the parameter REMOTE COMMS SEL
of the COMMS CONTROL function block is Set (= 1).
Setpoint Reached
This bit is set (=1) if the Reference Ramp is not ramping.
Internal Limit Active
This bit is set (=1) if, while in vector control mode, the speed limit has reached the torque limit;
or, while in Volts/Hz mode, the open loop current limit is active.