22
8903/RS RS485 Communications Interface
External Control of the Drive
Communications Command
When sequencing is in the Remote Comms mode, the sequencing of the Drive is controlled by
writing to the COMMS COMMAND (PREF 95.05, Modbus Holding Register 7091).
The COMMS COMMAND parameter is a 16-bit word based on standard fieldbus drive profiles.
Some bits are not implemented in this release (see “Supported” column of the table below).
Bit
Name
Description
Supported
Required
Value
0
Switch On
OFF1 Operational
9
1
(Not) Disable Voltage OFF2 Coast Stop
9
2
(Not) Quick Stop
OFF3 Fast Stop
9
3 Enable
Operation
9
4
Enable Ramp Output
=0 to set ramp output to zero
1
5
Enable Ramp
=0 to hold ramp
1
6
Enable Ramp Input
=0 to set ramp input to zero
1
7
Reset Fault
Reset on 0 to 1 transition
9
8
0
9
0
10
Remote
=1 to control remotely
1
11
0
12
0
13
0
14
0
15
0
Switch On
Replaces the RUN FWD, RUN REV and NOT STOP parameters of the SEQUENCING
LOGIC function block. When Set (=1) is the same as :
RUN FWD
=
TRUE
RUN REV
=
FALSE
NOT STOP
=
FALSE
When Cleared (= 0) is the same as :
RUN FWD
=
FALSE
RUN REV
=
FALSE
NOT STOP
=
FALSE