21
8903/RS RS485 Communications Interface
Accessing Fixed Parameters Only
If DSE registers are not required and only fixed parameters (PREFs) are to be accessed then
follow the instructions above for configuring the RS485 option but make sure no unused
registers are listed in the dialog box.
RS485 Status Information
The RS485 function block in DSE provides status information about the RS485 bus interface.
When online, the address and baud rate can be found by clicking the right mouse button over
the “Address” or “Baud” text and selecting
Get
from the menu.
The function block also provides two status outputs that can be wired to: PROCESS ACTIVE
and LAST TX STATUS.
PROCESS ACTIVE
Logic value:
True (T) indicates that the Modbus interface has received a
frame addressed to the node within the timeout period, or, if
the timeout period is disabled, the first frame has been
received.
The LAST TX STATUS output gives the exception error code of the last transmitted frame or 0
if there was no error. This output could be used with the LOGIC::LOOKUP function block to
determine a particular state.
LAST TX STATUS
Enumerated value:
Status Run
0:
NONE
1:
ILLEGAL
FUNCTION
2:
ILLEGAL
ADDRESS
3:
ILLEGAL
DATA
VALUE