
DOC-0017-08-EN: AC20 Series Ethernet/IP Option
DOC-0017-08-EN-B
04.04.2023
23 (46
)
9.2 List of process data
Read / Write Process Data mapping list for master/PLC
AC20 Input Mapping
Data Type
Byte
Comments
PLC Module
1212 Input Demultiplexer 1
WORD
2
Control Word
Output
2061 Input B Value Func 1
REAL
4
Speed Setpoint
0584 Digin Invert
WORD
2
Invert digital input
0626 Digout Invert
WORD
2
Invert digital Output
0497 Remote reverse
BOOL
1
Invert motor Rotation
0498 Rem Trip Reset
BOOL
1
Trip Reset
Total Byte Size
12
AC20 Output Mapping
Data Type
Byte
Comments
PLC Module
0507 Status Word
WORD
2
Status Word
Output
0462 Reference
REAL
4
Speed Reference
0103 Speed rpm
REAL
4
Speed Feedback
0534 Anin1 Value
REAL
4
Analog In1 Value
0540 Anin2 Value
REAL
4
Analog In2 Value
0558 Anout1 Value
REAL
4
Analog Out1 Value
0563 Anout2 Value
REAL
4
Analog Out2 Value
0610 Digin Word
WORD
2
Digital Input state
0625 Digout Word
WORD
2
Digital Output state
Total Byte Size
30