NTRODUCTION

The APR3-HUB2 is a
non-addressable module that
extends and divides the control
panel’s bus into two completely
isolated bus outputs (two for each
connected APR3-HUB2). It extends
the bus by regenerating the signal
between the control panel and its
modules. Should one bus output
experience trouble or tampering, the
other will remain unaffected. The
hub monitors the signal between the
control panel and modules on each
output. If the hub detects a loss of
signal integrity it will cut off the
troubled output until proper
communication is reestablished. 

If a hub’s output experiences trouble or tampering, the control panel
will generate a missing module trouble for every module connected
on that output.

I

NSTALLATION

Connecting the APR3-HUB2

Connect the APR3-HUB2’s four input terminals labelled 

RED

BLK

GRN

,

 and

YEL

 to the corresponding terminals of the control panel as shown on the back

page (Figure 2 “Connecting the APR3-HUB2”).

Extending the Bus

The APR3-HUB2 has two independent bus output terminals (labeled “OUT”) to
connect system modules. From a hub, you can connect modules in a serial or
“daisy-chain” configuration up to a distance of 3000ft (914m) for Digiplex and
DigiplexNE panels and 250ft (76m) for a Spectra panel as shown on the back
page (Figure 2 “Connecting the APR3-HUB2”). 

Each hub on the bus requires the connection of two power
supplies (one for each bus output terminal). Use either an
external power supply such as the PS-817 for Spectra or a
supervised power supply such as the DGP2-PS17 for Digiplex
and DigiplexNE. In addition, each power supply requires its own
transformer. Alternate configurations may result in improper
operation or damage to the system.

The APR3-HUB2 is non-addressable, therefore you can connect an
unlimited amount of hubs to the bus network without affecting the
total number of modules supported by the control panel.

Figure 1: Overview of the APR3-HUB2

Visual Feedback 

The APR3-HUB2 has on-board LEDs to display activity status. These are:

WDG LED:

Flashes to show proper hub operation.

ERROR LED:

Flashes to show a network fault.

DATA LED:

Flashes to show network communication

 

between modules to control panel.

Troubleshooting

In the event that LEDs display the following status:

WDG LED does not flash:

• Verify that the power supply for the input
   is properly connected.

ERROR LED Flashes:

• Verify that the power supply for the output
   is properly connected.
• Verify for wire shorts between the output’s
   

GRN

 

and 

BLK

 

wires.

• Verify for wire shorts of connected

 

  modules on the affected output.
• Remove any relay, hardwired, or non bus

 

  modules connected on the output, as this
  will affect communication. 

S

PECIFICATIONS

 

Power input:

Typically 12-16Vdc

Current consumption:

Typically 24mA. (50mA max)

Distance from panel:

Digiplex/DigiplexNE:

 

18AWG = 3000ft (914m) or 
22AWG = 1000ft (305m)

Spectra:
18AWG or 22AWG = 250ft (76m)

Distance of each output:

Digiplex/DigiplexNE:
18AWG = 3000ft (914m) or

 

22AWG = 1000ft (305m)

Spectra:
18AWG or 22AWG = 250ft (76m)

Operating temperature:

0°C to 50°C (-4°F to 122°F)

Compatibility:

Any Spectra, Digiplex, or

 DigiplexNE 

control 

panel

Since the APR3-HUB2’s is non-addressable,

 the Winload software

will not recognize the APR3-HUB2. Winload will recognize
addressable modules connected to hubs throughout the bus
network.