Paradox Spectra 1759EX V1.0 Скачать руководство пользователя страница 10

8   

R

EFERENCE

 & I

NSTALLATION

 M

ANUAL

 

  

2.5

AUXILIARY POWER TERMINALS

The auxiliary power supply terminals can be used to power motion detectors, keypads and other modules or accessories in the
security system. A fuseless circuit protects the power supply against current overload and automatically shuts down if the current
exceeds 1.1A. If this occurs, the Maximum Auxiliary Current failure will appear in the keypads’ Trouble Display (see page 47).
Therefore, the combined current consumption of devices connected to the auxiliary power supply should not exceed 700mA. If
the auxiliary output is overloaded and is shut down, you must disconnect all loads from the output for at least 10 seconds before
reconnecting any load back to the auxiliary output.

Modules with the APR- prefix are compatible with the Spectra 1759EX and Digiplex. Modules with the APR3- prefix are
compatible with the Spectra 1759EX, Digiplex and DigiplexNE.

2.6

TELEPHONE LINE CONNECTION

In order to report system events to the central station, you must connect the incoming telephone company wires into the TIP and
RING connections of the control panel and then run the wires from T1 and R1 to the telephone or telephone system as shown in
Figure 2.2 on page 7.

2.7

BELL OUTPUT CONNECTION

The BELL+ and BELL- terminals power bells, sirens and other warning devices requiring a steady voltage output during an alarm.
The bell output supplies 12VDC upon alarm and can support one 30-watt or two 20-watt sirens. The bell output uses a fuseless
circuit and will automatically shut down if the current exceeds 3A. When this occurs the Maximum Bell Current failure will only
appear in the keypads’ Trouble Display (see page 47) during an alarm. If the load on the BELL terminals returns to normal, the
control panel will re-instate power to the BELL terminals during the next alarm. When connecting sirens, please verify correct
polarity. Connect the positive lead to the BELL+ terminal and the negative lead to the BELL- terminal of the control panel as
shown in Figure 2.2 on page 7.   

If the BELL output is not being used, the Bell Disconnected failure will remain in the keypads’ Trouble Display
(see page 47)
. To avoid this connect a 1K

 resistor across the BELL terminals. 

2.8

PROGRAMMABLE OUTPUT CONNECTIONS

When a specific event occurs in the system, a PGM can reset smoke detectors, activate strobe lights, open/close garage doors
and much more.

2.8.1

A

LARM

 R

ELAY

 

AND

 PGM

S

 

The Spectra 1759EX control panel includes two on-board programmable outputs (PGMs). For details on how to program the
PGM, refer to PGM Programming on page 39. PGM1 can support up to 150mA while PGM2 supports up to 2.5A (see Figure 2.3
on page 9)
 and can be used as a strobe output (see page 40). The PGMs are limited by the power source being used. If powered
by:
• The 

AUX

 terminals. The current consumption of the 

AUX

 terminals cannot exceed 700mA. Therefore, whatever devices are con-

nected to the 

AUX

 terminals (i.e. modules and PGMs) cannot exceed 700mA combined. For example, if there are six modules con-

nected to the 

AUX

 terminals that are using 600mA and you wish to power the PGM using the 

AUX

 terminals, the PGM’s current

consumption will not 100mA.

• An external power supply. If using an external power supply, the current consumption cannot exceed 150mA for PGM1 and 2.5A for

PGM2. If the external power supply’s current consumption limit is less than that of the PGM it is connected to, than the current con-
sumption will not exceed the power supply’s current limit.  

The Spectra 1759EX control panel also has a 5A relay. This relay can be connected as shown in Figure 2.3 on page 9. The Alarm
Relay can be programmed to follow the bell output or the activation and deactivation of the Global PGM (see Alarm Relay
Options
 on page 40).

Table 2: Current Consumption Table

Modules

Current Consumption

Typical

Maximum

Spectra 1686H and 1686V 10-Zone LED Keypad

62mA

 116mA

Spectra 1689 16-Zone LED Keypad

50mA

 117mA

Spectra 1641 LCD Keypad

60mA

 80mA

4-Zone Hardwire Modules (APR3-ZX4/SPC-ZX4)

12mA

 12mA

8-Zone Hardwire Modules (APR3-ZX8/SPC-ZX8)

30mA

 30mA

4-PGM Output Module (APR3-PGM4)

13mA

 150mA

Printer Module (APR3-PRT1)

22mA

 40mA

InTouch Voice-Assisted Arm/Disarm Module (APR3-ADM2)

70mA

105mA

Motion Detectors (see detector instructions for details)

10 to 50mA

Содержание Spectra 1759EX V1.0

Страница 1: ...1759EX V1 0 REFERENCE INSTALLATION MANUAL 1759EX...

Страница 2: ......

Страница 3: ...tions 28 One Touch Arming 28 Exit Delay 28 Bell Squawk On Arm Disarm With Keypad 29 Bell Squawk On Arm disarm with Remote Control 29 No Exit Delay When Arming with Remote Control 29 No Exit Delay Beep...

Страница 4: ...switch Arming 50 Panic Alarms 50 Auto Arming 51 Alarm Memory Display 51 Programming Chime Zones 51 Keypad Muting 51 Keypad Backlight 1686H and 1686V only 51 FCC WARNINGS 52 INDEX 54 LIST OF TABLES Tra...

Страница 5: ...own Beep on Exit Delay Programmable Delay Before Alarm Transmission and Recent Closing Report Regular Arming Stay Arming Instant Arming Force Arming One Touch Arming Auto Arming or Keyswitch Arming 25...

Страница 6: ...iendly keypad will complete any installation 1 3 3 SPECTRA 1641 LCD KEYPAD The 1641 is a 32 character programmable LCD keypad which includes a zone input as well as a PGM output View zone event and tr...

Страница 7: ...voice dialer take over Compatible with any control panel the Paravox will verbally report system status by phone advising of detection of burglary fire flood or any other situation programmed to gene...

Страница 8: ...e grounded to the cold water pipe 2 3 AC POWER Do not use any switch controlled outlets to power the transformer Connect the transformer as shown in Figure 2 1 on page 6 Use Table 1 to determine the r...

Страница 9: ...ns refer to Configuring The LED Keypads on page 12 Refer to Single Zone Inputs on page 9 Refer to AC Power and Backup Battery Connections on page 6 To connect the 5A Alarm Relay and the PGMs refer to...

Страница 10: ...If the BELL output is not being used the Bell Disconnected failure will remain in the keypads Trouble Display see page 47 To avoid this connect a 1K resistor across the BELL terminals 2 8 PROGRAMMABL...

Страница 11: ...on page 16 Figure 2 4 Single Zone Input Connections 2 10 KEYPAD AND KEYPAD ZONE CONNECTIONS To connect the keypads to the control panel remove the back cover and wire the GRN YEL RED and BLK terminals...

Страница 12: ...minals Once a keyswitch is connected it must be assigned to a zone and its parameters must be programmed see Zone Programming on page 16 and Keyswitch Options on page 21 2 12 FIRE CIRCUITS When a zone...

Страница 13: ...126 to 138 and 302 to 348 each option from 1 to 8 represents a specific feature or option Press the key corresponding to the desired option and the corresponding light will illuminate or the option n...

Страница 14: ...istor be connected refer to Spectra 1759EX Control Panel Overview on page 7 for more details Key 2 OFF EOL disabled Key 2 ON EOL enabled default Key 3 On Board Tamper Key 3 enables or disables the key...

Страница 15: ...ORY KEY Copy the sections of one Spectra control panel into the Paradox Memory Key PMC 3 Then copy the contents of the Memory Key into as many Spectra control panels as needed Each panel is programmed...

Страница 16: ...tions The System Master Code can be 4 or 6 digits in length see section 4 1 where each digit can be any digit from 0 to 9 To change the System Master Code press ENTER INSTALLER CODE 301 new 4 or 6 dig...

Страница 17: ...ming is dependent on the other User Code Options selected Please note that with the Arm Only option the user can cancel a recently armed system by re entering the access code before the end of the Exi...

Страница 18: ...modules to the same expansion input 5 2 REASSIGN KEYPAD ZONE 2 Section 126 General Options Option 7 OFF Reassign Keypad Zone 2 Disabled default Option 7 ON Reassign Keypad Zone 2 Enabled Reassign Key...

Страница 19: ...e s partition assignment and how the control panel will react when an alarm condition occurs on that zone These Zone Parameters are programmed into one section as detailed in Figure 5 1 on page 18 Onl...

Страница 20: ...ition may require a different Entry Delay 5 5 2 ENTRY DELAY 2 Sections 001 to 015 Zones 1 to 15 First Digit 2 Entry Delay 2 zones are identical to the Entry Delay 1 zones see section 5 5 1 except it u...

Страница 21: ...collection 5 6 EXCLUSIVE ZONE DEFINITIONS The following three zone definitions can only be used for devices connected directly to the control panel s on board input terminals When a zone is programmed...

Страница 22: ...ounter the control panel will no longer generate an alarm for that zone To program the Auto Zone Shutdown Counter key in the desired limit 000 Disabled 001 to 015 Default 5 into section 089 The Auto Z...

Страница 23: ...ON Delay Alarm Transmission Enabled for Selected Zone When an alarm condition occurs on a zone with this option enabled the control panel enables the bell siren output but does not report the alarm to...

Страница 24: ...8 represent expansion inputs 1 to 8 respectively For example section 601 is assigned to expansion input 1 section 602 is assigned to expansion input 2 etc refer to Table 6 Each Expansion Input represe...

Страница 25: ...ll advise you of the transmitter s signal strength This feature cannot be used with any remote controls assigned to the control panel 6 3 SERIAL NUMBER DISPLAY Section 630 This feature will display th...

Страница 26: ...to section 6 4 1 on page 24 for instructions on enabling check in supervision Options 2 and 5 must match the jumper settings of the assigned transmitters For example if the check in supervision is se...

Страница 27: ...arm all the areas assigned to the User Access Code see section 6 5 4 on page 25 Sections 711 to 718 represent the remote controls assigned to sections 731 to 738 refer to section 6 5 2 on page 25 For...

Страница 28: ...__ ____ ____ ____ A B C D A B C D A C B D Remote Control 4 715 ____ ____ ____ ____ ____ ____ ____ ____ A B C D A B C D A C B D Remote Control 5 716 ____ ____ ____ ____ ____ ____ ____ ____ A B C D A B...

Страница 29: ...RCE key before entering their User Access Code 7 4 RESTRICT ARMING ON BATTERY FAIL Section 130 Arming Disarming Options Option 5 OFF Permit arming on battery failure default Option 5 ON Restrict armin...

Страница 30: ...e without movement you wish the control panel to wait before arming and or sending the No Movement report code If No Movement Auto Arming is disabled the control panel can still send the No Movement r...

Страница 31: ...Disarming Options Option 5 OFF No Exit Delay Beeps and No Bell Squawk When Stay Arming Disabled default Option 5 ON No Exit Delay Beeps and No Bell Squawk When Stay Arming Enabled With this feature e...

Страница 32: ...pass definition This means the control panel will ignore any tampers detected on a bypassed zone With option 3 off Tamper Recognition ignores the bypass definition This means the control panel will ge...

Страница 33: ...anic alarm is activated the control panel can ignore the disarm signal from a remote control for a specified period This prevents an aggressor from disarming the system by remote control during a pani...

Страница 34: ...Codes Option 6 ON Call Telephone 2 for Tamper Restore Report Codes Section 138 Option 1 ON Call Telephone 1 for Trouble Restore Report Codes Option 2 ON Call Telephone 2 for Trouble Restore Report Cod...

Страница 35: ...TIMED AUTO ARMING A partition has armed itself at the programmed time see page 27 LATE TO CLOSE Reports every day at the time specified by the Auto Arm Timer see page 28 NO MOVEMENT A partition has a...

Страница 36: ...T CODES Sections 201 to 204 A report code can be programmed for each of the 15 available zones Whenever a tampered zone is restored the control panel can send the appropriate report code to the centra...

Страница 37: ...are used please refer to Event Call Direction on page 37 and Reporting Formats in section 9 5 After the Maximum Dialing Attempts see page 37 to one central station telephone number have failed the co...

Страница 38: ...Report Codes Press the FORCE key to enter a 0 value When using the All Codes format the control panel will automatically generate Contact ID Report Codes for every event in sections 160 to 213 Refer...

Страница 39: ...ult When using Pulse dialing you can select one of two Pulse Ratios Although most European countries use the 1 2 pulse ratio the 1 1 5 ratio may provide better results in some cases The same applies f...

Страница 40: ...ys at 1 PM 9 17 POWER FAILURE REPORT DELAY Section 086 001 to 255 minutes Default 15 minutes The control panel will transmit the AC Failure report code programmed in section 205 after the Power Failur...

Страница 41: ...round therefore cutting power to any devices connected to it PGM1 A programmable output that provides up to 150mA Refer to Alarm Relay and PGMs on page 8 PGM2 PGM2 is a programmable output that can pr...

Страница 42: ...PGM output to be normally open N O or normally closed N C by enabling or disabling options 4 5 and 6 in section 126 Option 4 OFF PGM1 Normally Closed Default Option 4 ON PGM1 Normally Open Option 5 OF...

Страница 43: ...Charge Current 350mA default Option 5 ON Battery Charge Current 700mA 40VA transformer required 11 5 PARTITIONING Section 127 General Options Option 1 OFF Partitioning Disabled default Option 1 ON Pa...

Страница 44: ...will send the Zone Tamper report code as originating from partition 1 A Tamper Zone Wiring Failure will also appear in the keypads Trouble Display see page 47 When Reassign Keypad Zone 2 is enabled s...

Страница 45: ...ith the APR prefix are compatible with Spectra versions 2 0 and higher and Digiplex Modules with the APR3 prefix are compatible with Spectra versions 2 0 and higher Digiplex and DigiplexNE 11 13 PRINT...

Страница 46: ...el will follow the zone s Alarm Types setting see page 20 7 ON 8 ON Audible Alarm When a tamper occurs on an Omnia wireless transmitter zone in a disarmed system it functions the same as the Trouble O...

Страница 47: ...control panel will answer the call You must wait at least 10 seconds before attempting the second call or the control panel will think it is the same call 12 2 PANEL IDENTIFIER Section 141 0000 to FF...

Страница 48: ...communication is interrupted before completing transmission or if after two attempts communication is not established the system will wait until the Event Buffer attains another 50 capacity before att...

Страница 49: ...elay in section 086 The AC LED turns back on as soon as power is restored 4 Bell Disconnected This trouble occurs when a bell or siren is not connected to the bell output terminals If you are not usin...

Страница 50: ...ed partition If you make a mistake the FORCE or 16 Keypad Fault If the keypad is no longer communicating with the control panel the TBL or TRBL will flash the FORCE key will illuminate the LCD keypad...

Страница 51: ...Any open Force Zones at the time of arming will be considered deactivated by the control panel If during this period a deactivated zone is closed the control panel will revert that zone to active sta...

Страница 52: ...t Delay At the end of the Exit Delay period the control panel will switch to Force Arming 13 10 KEYSWITCH ARMING A keyswitch can be used to arm and disarm the system Assign the keyswitch to a specific...

Страница 53: ...ep this means the chime feature has been enabled for that zone If the keypad emits a rejection beep this means the chime feature has been disabled for the corresponding zone 16 ZONE LED KEYPAD Press a...

Страница 54: ...t installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installat...

Страница 55: ...ces de charge de l ensemble des dispositifs ne d passe pas 100 La certification d Industrie Canada s applique seulement aux installations d appareils utilisant un transformateur approuv par l Associat...

Страница 56: ...awk On Arm disarm with Remote Control 29 Burglary Zones 24 Hr 19 Buzzer Zone 19 Bypass Options Supervision 44 Bypass Programming 49 Bypass Recall Feature 50 Bypass Zones 20 C Call Back Feature 46 Call...

Страница 57: ...back Upon Stay Arming 29 No Exit Delay When Arming with Remote Control 29 No Movement Auto Arming 28 Number of Rings 45 O One Touch Arming 28 50 Options Alarm 29 Arming and Disarming 27 Auto Arming 28...

Страница 58: ...hone Number PC 45 Telephone Numbers 35 Test Report Automatic 38 Test Report Manual 43 Timed Auto Arming 27 Transformer Requirements 6 Trouble Display 47 U Upload Download Software 11 User Code Options...

Страница 59: ......

Страница 60: ...780 boul Industriel St Eustache Montr al Qu bec J7R 5V3 Fax 450 491 2313 www paradox ca PRINTED IN CANADA 02 2002 1759EX EI00...

Отзывы: