Magellan / Spectra SP
17
*This option applies to all hardwired zones (panel, keypad, ZX8)
Zone Timers (MG Series)
Note that When both ATZ and EOL are enabled, zone speed should not be set below 300ms.
Zone Timers (SP Series)
NOTE:
When both ATZ and EOL are enabled, zone speed should not be set below 300ms.
[6] & [7]
Supervision Options
[8]
Generate supervision on bypassed zone
No
Yes
[706]
General Zone Options
Option
OFF
ON
[1]
Check-in supervision time (except SP4000)
24 hours
80 minutes
[2]
EOL resistors*
Disabled
Enabled
[3]
Zone Input 1 becomes a 2-wire smoke input (except SP5500/SP4000)
Disabled
Enabled
[4]
ZX8 ID A (Panel + 1) Input 1
Zone input
Tamper input
[5]
ZX8 ID B (Panel + 9) Input 1
Zone input
Tamper input
[6]
ZX8 ID C (Panel + 17) Input 1
Zone input
Tamper input
Section
MG5000
MG5050
Data
Description (Default 060)
[041]
Zone 1
(Z1)
(Z1)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 1 Speed
[042]
Zone 2
(Z2)
(Z2)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 2 Speed
[043]
Zone 3
(Z1 ATZ)
(Z3)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 3 Speed
[044]
Zone 4
(Z2 ATZ)
(Z4)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 4 Speed
[045]
Zone 5
(Z5)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 5 Speed
[046]
Zone 6
(Z1 ATZ)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 6 Speed
[047]
Zone 7
(Z2 ATZ)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 7 Speed
[048]
Zone 8
(Z3 ATZ)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 8 Speed
[049]
Zone 9
(Z4 ATZ)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 9 Speed
[050]
Zone 10
(Z5 ATZ)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 10 Speed
[051]
Zone 11
____/____/____
(000 to 255) x 10ms
Hardwire Zone 11 Speed
[052]
Zone 12
____/____/____
(000 to 255) x 10ms
Hardwire Zone 12 Speed
[053]
Zone 13
____/____/____
(000 to 255) x 10ms
Hardwire Zone 13 Speed
[054]
Zone 14
____/____/____
(000 to 255) x 10ms
Hardwire Zone 14 Speed
[055]
Zone 15
____/____/____
(000 to 255) x 10ms
Hardwire Zone 15 Speed
[056]
Zone 16
____/____/____
(000 to 255) x 10ms
Hardwire Zone 16 Speed
Section SP4000
SP5500
SP6000
SP7000* Data
Description
(Default
060)
[041]
Zone 1
(Z1)
(Z1)
(Z1)
(Z1)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 1 Speed
[042]
Zone 2
(Z2)
(Z2)
(Z2)
(Z2)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 2 Speed
[043]
Zone 3
(Z3)
(Z3)
(Z3)
(Z3)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 3 Speed
[044]
Zone 4
(Z4)
(Z4)
(Z4)
(Z4)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 4 Speed
[045]
Zone 5
(Z1 ATZ) (Z5)
(Z5)
(Z5)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 5 Speed
[046]
Zone 6
(Z2 ATZ) (Z1 ATZ) (Z6)
(Z6)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 6 Speed
[047]
Zone 7
(Z3 ATZ) (Z2 ATZ) (Z7)
(Z7)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 7 Speed
[048]
Zone 8
(Z4 ATZ) (Z3 ATZ) (Z8)
(Z8)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 8 Speed
[049]
Zone 9
(Z4 ATZ) (Z1 ATZ)
(Z9)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 9 Speed
[050]
Zone 10
(Z5 ATZ) (Z2 ATZ)
(Z10)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 10 Speed
[051]
Zone 11
(Z3 ATZ)
(Z11)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 11 Speed
[052]
Zone 12
(Z4 ATZ)
(Z12)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 12 Speed
[053]
Zone 13
(Z5 ATZ)
(Z13)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 13 Speed
[054]
Zone 14
(Z6 ATZ)
(Z14)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 14 Speed
[055]
Zone 15
(Z7 ATZ)
(Z15)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 15 Speed
[056]
Zone 16
(Z8 ATZ)
(Z16)
____/____/____
(000 to 255) x 10ms
Hardwire Zone 16 Speed
* SP7000: For zones 17-32 (ATZ), the zone timer is set at 0.6 seconds.
[6]
[7]
RF Zone Supervision Options (except SP4000)
Keypad / Bus Module Supervision Options
OFF
OFF
Disabled Disabled
OFF
ON
Trouble only
Trouble only
ON
OFF
When disarmed: Trouble only
When armed: Follow zone’s alarm type
Trouble only
ON
ON
When disarmed: audible alarm
When armed: Follow zone’s alarm type
Trouble only