![Paradox IMPERIAL DIGIPLEX EVO ACM24D Скачать руководство пользователя страница 1](http://html.mh-extra.com/html/paradox/imperial-digiplex-evo-acm24d/imperial-digiplex-evo-acm24d_instructions_753388001.webp)
TM
ACM24D-EI00
PARADOX.COM
Printed in Canada - 01/2009
Instructions
ACM24D 4-Wire Access
Control Module V1.0
The ACM24D Access Control Module can
control two doors and can support REX devices,
readers, locking devices and door contacts.
Door contacts that are connected to the
ACM24D are programmed using BabyWare
software and can be assigned to zones in the
Imperial system.
Installation
The ACM24D is a
standard 35mm
DIN rail module.
Using the
supplied DIN rail,
the ACM24D can
be mounted in any
location.
Alternatively, it
can be mounted in
a standard DIN rail enclosure. To attach the
module, align the top of the DIN rail as shown in
Figure 1 and apply pressure to the module until it
clicks into place. To remove the ACM24D from a
DIN rail, pull the release clip and remove the
module.
To facilitate installation and servicing, the
ACM24D terminals can be detached from the
module. Wires can be labeled using the supplied
tie wraps.
Door contacts connected to the system follow
the control panel’s EOL definition. When EOL is
enabled and door contacts are not used, place a
1k
Ω
resistor across the
CT
and
C
input terminals.
If EOL is disabled, use a jumper. If the REX
device is not used, place a jumper across the
RX
and
C
terminals.
Stand-Alone Mode
The ACM24D stores all access codes and cards
in memory. If panel communication is lost, the
ACM24D will continue to function normally.
Events will be stored in memory. When
communication is restored, events are
automatically uploaded to the panel.
Upgrading the Firmware
Imperial
The firmware of the ACM24D can be in-field
upgraded through the V32’s RS485 ACCESS
port using BabyWare.
EVO/DGP
The ACM24D firmware can be upgraded through
WinLoad using the CV4USB RS-485/RS-232
Converter. Refer to the firmware upgrade
instructions found at: paradox.com - Software -
WinLoad - Firmware Upgrade Instructions.
Imperial V32
EVO48, EVO192
DGP-848, DGP-NE96, EVO96
Figure 1: DIN Rail Mounting
Release
clip
35mm
DIN rail
Communication LED Feedback
Bus
RX
TX
Condition
off
green - flash
green - flash OK (panel communication in progress)
off
off
off
OK (no data RX/TX)
red
off
off
Short on GRN or YEL
red off
green
Communication failure / Too many modules on
Multibus
red green
green
Multibus
lines reversed (Green / Yellow)
red flash
off
off
Bus power too low
red flash
green - flash
green - flash Locate mode
blue ---
---
Communication
with
V32 panel / Multibus mode
blue flash
off
off
Firmware upgrade in progress
Power LED Feedback
LED
Colour
Condition
AC
green
AC or DC power is supplied
CHRG
green
Battery is low / charging
green (less than 4 sec.)
Battery test
Door LED Feedback
DOOR1 and DOOR2 manual control buttons display door status and can override door
programming. Manually unlocked doors remain unlocked for the minimum period
programmed in BabyWare.
Colour
Condition
green on
Door unlocked
red on
Door locked
Door Labels
Space is provided to label
each door.
Fuse
- not used
Detachable Terminals
Pry with screwdriver if
necessary.
Locate Mode
•
For Imperial panels, a Module Locate can be started or stopped using BabyWare software
or by pushing the module’s LOC button. When a Module Locate is initiated, a flashing
occurs of the module’s LEDs (BUS RX and TX flash at 1Hz) as well as the module’s
representation in BabyWare.
•
For DGP/EVO panels, a Module Locate can be initiated using section [4002] (EVO) or
[952] (DGP-48 / DGP-848). To end a Module Locate, press the LOC button.
Reader LED Feedback
red flash
Reader auxiliary power failure
red on
Reader is missing
green on
Readers OK
off
No reader programmed for this door
Transformer Sharing
Modules can share a central AC
transformer (16 to 24V
AC
) throughout the
system. Ensure that the total power output
of the transformer is respected.
.
16 / 24 Vac
16 / 24 Vac
ACM24D
ACM24D
Connect to other
modules
compatible with
transformer
sharing.
Transformer
EVO / DGP Programming
When used on an EVO/DGP system, the ACM24 appears in WinLoad as two ACM12 modules.
Serial Numbers
Example: ACM24D = 3500556A ACM12 #1 = 3500556
A
ACM12 #2 = 3500556
B
(plus 1 number / letter)