- Advanced Analogue Conventional Fire Alarm & Extinguishing Control Panel
3.1 Zone descriptions (ALM1.1)
This screen shows a scrollable list of all installed zones along with their description.
Selecting a zone (with the up/down arrows) and pressing <ENTER> will request A.L.2
code and enter the zone description editor.
————= ALL ZONES =————
>1: ZONE 01
2: ZONE 02
3: ZONE 03
Figure 5.
Zones descriptions screen
3.2 Zones overview (Zone states) (ALM1.2)
X034RLSD
_________________
____________________
____________ NO FLTR
Figure 6.
Zones overview screen
This screen shows an overview of all the installed zones. Each zone is represented by
one LCD character. Each character space may have one of the following characters
signifying a zone condition:
|
|:
Zone active and idle.
|Z|:
Zone is in fault condition.
|R|:
Relay corresponding to the zone is in fault.
|F|:
Zone and corresponding relay in fault.
|A|:
Zone is in alarm.
|I|:
Intellizone is in pre-alarm state.
|a|:
Zone is in alarm and corresponding relay is bypassed.
|z|:
Zone is bypassed.
|r|:
Relay is bypassed.
|b|:
Zone and corresponding relay are bypassed.
|X034|:
Cross-zone area in prerelease. 034 is shown as an example and indicates the
time remaining before the release state is reached (in this case 34 seconds).
|H034|:
Cross-zone area in prerelease state and
HOLD
button pressed. 034 is shown
as an example and indicates the time remaining before the release state is reached (in
this case 34 seconds).
|RLSD|:
The cross-zone area is in the Released phase.
|S|:
Cross-zone stopped from HOLD button in Pre-released phase.
|HOLD|:
Cross-zone in the Released phase but stopped from the HOLD button.