For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2013
PN575B
Page 1 of 4
Specifications
• Cable jacket diameter 0.285 in. max.
• Maximum conductor insulation diameter 0.041 in.
• Panduit recommends T568B wiring scheme for use
with cable constructed with the brown pair opposing
the orange pair.
Conductor holes and Contact slots
1
Thread boot and collar onto the cable first.
Remove 2.0" of the outer jacket from the cable end using
wire stripping tool (CJAST).
Remove matrix foil to expose twisted pairs.
Fan twisted pairs into respective quadrants. The brown
pair should be opposite the orange pair.
When a cable spline (X-shaped filler) is present, cut spline
flush to fanned pairs using wire snipping tool (CWST).
Thread on boot
and collar first!
(Cable ends 1 & 2)
90°
CWST
Strain Relief Boot
Strain Relief Collar
Divider
Load Bar
Plug Housing
Load Bar
1
8
Divider
Conductor slots and “V” channel
2
Note orientation of the divider depending on cable end 1
or cable end 2. The “V” channel should be aligned with the
green pair.
Insert divider posts into the cable. If the cable has an
internal spline, insert divider posts into the brown and
orange quadrants of the spline.
BLU
GRN
“V” channel
BRN
ORG
GRN
BLU
BRN
ORG
(Cable end 2)
(Cable end 1)
“V” channel
3
Arrange conductors to T568B wiring scheme while
minimizing untwist and smooth conductors.
Seat conductors into proper divider slots while holding
divider near the end of the cable jacket.
“V” channel
(Cable end 1)
(Cable end 2)
T568B Wiring Scheme
T568B BRN
8
WHT
7
BRN/
6
GRN WHT
5
BLU/
4
BLU WHT
3
GRN/
2
ORG WHT
1
ORG/
Pin #
“V” channel
Conductor holes
Contact slots
Divider post
Pins
* Denotes packaging quantity.
Category 6A UTP Modular Plug
for Panduit Patch Cable
T568B & T568A
Part Number: SP6X88P-*