![Panduit Synapsense ThermaNode EZ Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/panduit/synapsense-thermanode-ez/synapsense-thermanode-ez_installation-manual_3444372050.webp)
CABINET SENSOR HARDWARE INSTALLATION
MANUAL
49
the Status column.
7. Verify green checks
for each installed node in
the Status column.
A red “
X
” in the Input
columns indicates a
problem. Ensure the
node is ON, and check
for loose connections or
damaged wires.
8. Turn node off and on, allowing at least 15-20 minutes to rejoin the network
9.
Correct any errors and repeat the previous steps for software validation.
Proceed to Inspecting the Installation to complete the installation process
ThermaNode LEDs
The ThermaNode communicates status via Light Emitting Diodes (LEDs) visible through
a translucent plastic cover on the topside of the plastic case.
Typically, the sequence from an
OFF
state to normal operations may last from ten minutes
to over an hour, depending on the network environment in the data center. The diagram
below explains the typical sequence of colors displayed when the ThermaNode first
activates and connects to the appropriate wireless network.