Technical Reference 79-SZ 

 

Description 

Beacons can be used to aid guided patching and tracing operations in the data center. When a Move, 
Add, or Change (MAC) request or Trace operation between two PViQ panels is remotely initiated in 
SmartZone, it is not always obvious where the two panels are located.  Beacons, installed on top of 
each cabinet and properly configured in SmartZone, will illuminate when any panel located in the 
cabinet is involved in a MAC or Trace operation. The idea is to first guide the technician to the correct 
cabinet using the beacon and then further guide the technician to the correct port by looking at LEDs 
on the PViQ panel. 

 

Hardware 

 The hardware necessary to provide the beacon feature consists of 2 beacons, 1 beacon controller, 
and its power adapter.  

The beacon controller is actually a Xytronix relay controller, model X301, which switches 12VDC 
current on and off to each beacon as instructed to do so via SmartZone. 

Note

: SmartZone does not 

support relay controllers from other manufacturers. Each beacon controller controls 2 beacons which 
are connected to the beacon controller via 12AWG wires. 

Beacon Setup and Use with SmartZone

 

Applies to: 

SmartZone Users 

Objective: 

This Technical Reference describes the beacon controller and beacon 
hardware and setup necessary to work with SmartZone. It also describes 
the SmartZone setup and operation for beacons. 

Documentation 
Reference: 

Consult the manufacturer's website, www.controlbyweb.com, for current 
product documentation for the X301 WebRelay Controller. 

Pre-Requisites: 

The beacon controller firmware must be version 1.12 

 

Published: 

7/25/18

 

 

Содержание SmartZone

Страница 1: ...eature consists of 2 beacons 1 beacon controller and its power adapter The beacon controller is actually a Xytronix relay controller model X301 which switches 12VDC current on and off to each beacon a...

Страница 2: ...oy the beacon function every cabinet would need a beacon whereas only every other cabinet would need a beacon controller Bill of Materials The Bill of Material for the beacon beacon controller and ass...

Страница 3: ...lls adapter plugs for use in the U K EU and Australia The 2 wires of 12 volt side of the adapter are screwed down to the terminal block as shown in Appendix II Beacon Controller Firmware The beacon co...

Страница 4: ...s environment along with SNMP community strings SmartZone server IP address and beacon controller name IP Address The IP address is setup on the Network tab SNMP Community String In order for SmartZon...

Страница 5: ...panduit com 5 T E C H N I C A L R E FE R E N C E SmartZone Server IP address Set SNMP Enabled to Yes and enter the IP address of the SmartZone server next to SNMP Manager IP in the Advanced Network t...

Страница 6: ...Location Tree after the Beacon Controller is discovered It is important to have a unique name for each Beacon Controller to distinguish each one in SmartZone SmartZone setup for the Beacon Controller...

Страница 7: ...actually discover the beacons but will automatically add 2 beacons for every beacon controller it discovers SmartZone will join L1 and L2 to the name of the beacon controller to indicate the beacons...

Страница 8: ...one cannot discover the beacons that are connected to a beacon controller but it will automatically add 2 beacons and associate them with the beacon controller The association is shown in the Associat...

Страница 9: ...lluminate in SmartZone Trace Mode example Turn on Trace Mode for any panel port in a rack where a beacon is located As shown below port 3 for panel 1 in rack 1 is enabled for Trace Mode Port 3 is conn...

Страница 10: ...will also reflect it in graphical view For example by selecting graphical view for rack 1 the beacon is depicted in an illuminated state Returning the panels to secure mode turns off the beacons on t...

Страница 11: ...sued between any 2 panels in racks where beacons are located the beacons illuminate in the data center and SmartZone also reflects it in the GUI For example a disconnect request is made between a pane...

Страница 12: ...n the data center and SmartZone reflects this in the GUI As the technician physically removes one end of the patch cord one beacon turns off and SmartZone reflects this The remaining beacon continues...

Страница 13: ...end of the patch cord completing the MAC request both beacons turn off and SmartZone reflects this Operation of Beacons outside of SmartZone The beacons will illuminate based on Trace operations made...

Страница 14: ...acons in the racks the beacons will illuminate showing the technician the location of the rack where the other end of the patch cord is connected Location mode initiated via a telnet session It can be...

Страница 15: ...www panduit com 15 T E C H N I C A L R E FE R E N C E Appendix I Wiring Diagram 12V 12V 12V 12V NO NC C 12V 12V 12V 12V NO NC C beacon off beacon on GENERIC CIRCUIT...

Страница 16: ...ING METHOD Appendix II Bill of Materials Bill of Material to equip 2 cabinets with signal beacons ITE M DESCRIPTION MFR PART NUMBER Q T Y REMARKS 1 Power Supply Regulated 12VDC 1 5 Amp PS12VW1 5 B Xyt...

Страница 17: ...K Xytronix PSB UK 1 4 Cable unshielded twisted pair Belden 88442 22 AWG 0 0326mm2 Belden 88442 Quantity as required not to exceed 100ft 30m per beacon loop resistance 3 2 strip and tin ends recommende...

Страница 18: ...www panduit com 18 T E C H N I C A L R E FE R E N C E Appendix III Mounting Appendix IV Testing...

Страница 19: ...N I C A L R E FE R E N C E To test the wiring and operation open the web interface and go to the Control Page tab Click the Pulse button for Relay 1 The beacon for Relay 1 should flash Repeat for Rel...

Страница 20: ...www panduit com 20 T E C H N I C A L R E FE R E N C E End State The beacon setup and operation is complete...

Отзывы: