SMARTZONE UPS INSTALLATION MANUAL
70
Section 5
– Replacing Battery Cartridges
Internal Battery Cartridges in the 1-3kVA UPS Units (UVC024,
UVC036, UVC048, UVC072)
Replace battery cartridges with only the same SKU. It is recommended to replace all
battery cartridges in a system at the same time with new battery cartridges of the same
SKU for that unit (UPS and EBP).
1. Change the UPS in the system to the Bypass state, this will not allow the UPS to
transition to Battery state while the battery cartridges are being replaced.
2. Turn off the breaker on the back of all the EBP units in the system, this will reduce
arching while the battery connects and disconnects are being made.
Note:
All Battery
cartridges in the system should be changed at the same time, it is not recommended
to mix new battery cartridges and old battery cartridges in a system.
3. Remove the faceplate:
a. Press both sides of UPS faceplate until the latches release (see figure below).
Figure 82: Press the Latches to Remove Faceplate
b. Remove the faceplate (see figure below).