PVIQ™ CONNECTIVITY SYSTEM USER MANUAL V 1.0
110
Fiber I-Cord Disconnection
The following procedure provides instructions to disconnect a Fiber I-Cord connection
using a guided Move, Add or Change (MAC) order from the SmartZone Asset and
Connectivity Software Modules. Additional information on the SmartZone Asset and
Connectivity Software Modules can be found in the SmartZone Software User Manual.
1. Right-click the PViQ™ I-Cord connection icon of the desired switch port and
select
Disconnect
. Click
Save
. The SmartZone Asset and Connectivity Software
Modules send a MAC-delete-interconnect command to the patch panel. The
panel prompts by flashing the designated port LED red and displaying MAC
mode on front panel to the desired switch port.
Figure 87: Designated Port and PViQ™ Panel IU during a Fiber I-Cord
Authorized Remove
2. Unplug the Fiber I-Cord from the PViQ™ Fiber Patch Panel. The Port LED turns
off.
Figure 88: Designated Port after Remove is Complete
3. Right-click the connection cell and select PViQ™ I-Cord from the drop-down list.
Click
Save
to implement the change.
4. The panel signals end of MAC by returning to Secure mode. The SmartZone
Asset and Connectivity Software Modules trust that the far end has been
disconnected and replaces the PViQ™ I-Cord (connected) icon between the two
ports with a no connection icon.