SMARTZONE UPS USER MANUAL
89
Appendix A2: 10 to 20kVA Fault Codes & Alert
LEDs
The following Fault Code Table lists the available Warning and Critical Fault codes
shown on the display of the 10 to 20kVA 3-Phase UPS platform. The Buzzer will make a
continuous beep or periodic beeps (about once per second). The Alert LED will either
illuminate Yellow for Warning Alarms or Red for Critical Alarms. These may be subject
to change based on the core FW version loaded in the UPS.
If the Fault Code cannot be cleared, then contact Panduit Customer Technical Support
at
information.
•
Product SKU and serial number.
•
Detailed explanation of the fault, such as LCD display info, LED lights status, etc.
Fault
Code Fault Description
Fault
Type
Buzzer
LED
Action to Take
002 Rectifier Over
Temperature
Critical Continuous
Red
Alert On
Ensure that Ambient operating
temperature is at or below 40C.
Reduce the load
Check if the battery group is set
correctly
Remove ventilation obstructions.
Reboot UPS
003
Rectifier Parallel Signal
Error
Critical Continuous
Red
Alert On
Reboot the UPS unit
004 Rectifier Overcurrent
Warning
Periodic
Yellow
Alert On
Ensure that the source input
voltage is within the UPS operating
range
Reduce the load
Reboot the UPS unit
005
Rectifier Power Supply
Error
Critical Continuous
Red
Alert On
Reboot the UPS unit
007 Input SCR Error
Critical Continuous
Red
Alert On
Reboot the UPS unit