G5 PDU Installation Manual 

Содержание MS Series

Страница 1: ...G5 PDU Installation Manual...

Страница 2: ...ed Cord Retention 10 4 in 1 combination outlets 11 Locking Power Cord 11 Section 2 Installing the PDU 12 Vertical PDUs 12 Install Mounting Hardware 12 Vertical 0U PDU Single Installation 13 Vertical 0...

Страница 3: ...ounting Options 20 Mounting Hardware Installation 21 Grounding the PDU 22 Connecting the Ground Bonding Cable 22 Bonding 23 Section 3 Connecting the PDU 24 Connecting the PDU to a Power Source 24 Sect...

Страница 4: ...r Power Factor Corrected PFC input current If non linear loads are connected the nameplate current rating of the PDU must be reduced by a factor of 0 8 Follow these safety precautions when connecting...

Страница 5: ...r electric shock install this PDU in a temperature and humidity controlled indoor environment free of conductive contaminants Do not operate near water or excessive humidity 90 maximum noncondensing A...

Страница 6: ...and manage these outlets from a single power connection The PDUs can be managed from a Web interface or a Command Line Interface CLI and viewed from the local display Panduit PDUs are designed for use...

Страница 7: ...ges ranging from 208V 415V 1PH or 3PH Simply select the facility side cord set to match the power needs of the installation If your power needs ever change in the future just swap in a new facility si...

Страница 8: ...ull height versions and install vertically in the 0U space in the back of the rack There are also Half and Full height dual sided models that install vertically in the 0U space in the back of the rack...

Страница 9: ...U Example Universal Input PDU Example There is one exception to the different colored outlets per load segment The three phase half height dual sided model has two different load segments on each phas...

Страница 10: ...n feature This will allow you to secure the cord to the outlet without a cord retention bracket The Dual Sided PDU models to not include this feature to save space however those PDU models are locking...

Страница 11: ...tlet Image C or a C13 C15 C19 C21 outlet Image D without any modifications Merely plug in the corresponding power cord to the applicable outlet C D Locking Power Cord Optional locking power cords can...

Страница 12: ...s two different mounting hole locations on the sides and back of the PDU for the button installation to assist with mounting in a non Panduit racks When installing the mounting buttons use either moun...

Страница 13: ...erting the mounting buttons into the keyhole slots on the PDU mounting bracket in the rack Vertical 0U PDU Single Installation A single vertical unit can be installed with the outlets facing the cente...

Страница 14: ...U rack vertical units to be mounted on one side of the rack all units must be installed with the outlets facing in towards the center of the rack A B C NOTE A Two full height PDUs with outlets facing...

Страница 15: ...f the cabinet and circuit breakers facing the inside of the cabinet when viewing the cabinet from the rear A B NOTE One full height can be installed per side of rack whereas two half height models per...

Страница 16: ...h the uPDU interconnect with the facility side connector disconnected 3 Universal Input Connector uPDU interconnect must be fully secured to the mating PDU side connector with the facility side connec...

Страница 17: ...versal Input PDUs to PDU brackets NOTE When installing Universal Input PDUs with input cord at the top top three RUs might be obstructed at the back by the input cord plug Configuring Universal Input...

Страница 18: ...rating of the PDU 1 Reference the User Manual for instructions to connect to the Web interface 2 Navigate to the System Management page under setting System Management Navigation 3 Select Set Input Co...

Страница 19: ...6A3WYE UPDUCRD7 30A1L L UPDUCRD8 20A1L L 16A1L N UPDUCRD9 30A1L L 32A1L N UPDUCRD10 L21 30 UPDUCRD11 30A3DLT UPDUCRD12 50A1L L 1U PDUs Mounting Options This unit can be installed in any 1U location of...

Страница 20: ...INSTALLATION MANUAL Page 20 1 Install the cage nuts at the desired U location 2 Screw the mounting bracket ears into the RETMA rail surface at the U location where the cage nuts were installed 2U PDU...

Страница 21: ...21 IM054 REV 10 G5 INSTALLATION MANUAL Page 21 This unit can be installed in any U locations of the rack Mounting Hardware Installation 1 Install cage nuts at the desired U locations 2 Install the PDU...

Страница 22: ...chassis of the PDU The ground bonding screw is provided as an attachment point for conductors Use a ground bonding cable if the rack contains any conductors for functional grounding or bonding of ungr...

Страница 23: ...a bolt on solution Bonding This product contains an external earthing screw with a star washer which should be used for supplementary Earth bonding to the rack metalwork Bonding Minimum Requirements f...

Страница 24: ...ll circuit breakers on the PDU are set to On 3 Connect each PDU to an appropriately rated branch circuit NOTE Refer to the label on the PDU for the input ratings 4 Turn the feed circuit breaker On The...