Panduit DPOE24S1XY Скачать руководство пользователя страница 1

 
 

DPoE

™ 

Power Patch Panel 

User Manual 

For Parts DPOE24U1XY, DPOE24S1XY, DPOE12U1XY 

 

 

 

 

 

 

 

 
Copyright © 2008 PANDUIT Corp. All rights reserved. No part of this book shall be reproduced, stored in a retrieval 
system, or transmitted by any means, electronic, mechanical, photocopying, recording or otherwise, without written 
permission from 

PANDUIT

. No patent liability is assumed with respect to the use of the information contained herein. 

 
Although every precaution has been taken in the preparation of this book, 

PANDUIT

 assumes no responsibility for 

errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained 
herein. 

 

 
 
 

Part # PN378E 

Published October 2008 

Содержание DPOE24S1XY

Страница 1: ...ical photocopying recording or otherwise without written permission from PANDUIT No patent liability is assumed with respect to the use of the information contained herein Although every precaution ha...

Страница 2: ...rom another country The products presented in this user s guide are not designed intended authorized or warranted to be suitable for use as components in systems used in any life support or critical a...

Страница 3: ...Requirements 19 Installing the DPoE Element Manager Software 20 Connecting the DPoE Element Manager Host Computer to the DPoE Power Patch Panel 21 DPoE Element Manager Operation 21 Graphical User Int...

Страница 4: ...gures Figure 1 DPoE Power Patch Panel Front View 6 Figure 2 DPoE Power Patch Panel Rear View 7 Figure 3 System Level Opening Screen 22 Figure 4 View Panel Screen 31 Figure 5 View Device Screen SNMP Se...

Страница 5: ...DPoE Element Manager Log Messages 49 Table 13 DPoE Power Patch Panel Firmware Update LED Status 52 Table 14 Power Supplies Available from PANDUIT 53 Table 15 Package Contents 53 Table 16 PANDUIT Corp...

Страница 6: ...out the need for separate passive patch panels NOTE DPoE Power Patch Panels cannot be used for analog or non Ethernet devices While the DPoE Power Patch Panel may be used as a standalone device it can...

Страница 7: ...devices and allows centralized power management by the network operator Combining PoE Power with patch panel functionality for Ethernet Connections Other vendors use a separate Power Hub architecture...

Страница 8: ...e event of low power conditions a NMS working in conjunction with the DPoE Power Patch Panels can use the pre established port priorities to ensure mission critical ports on the network of panels cont...

Страница 9: ...0 watt rectifier for use in the DPOEPWRCU chassis CORD A Power cord for Australia CORD E Power cord for Europe CORD S15 Power cord for North America CORD J15 Power cord for Japan CORD U Power cord for...

Страница 10: ...Do not exceed a total length of 35 feet Verify the above contents arrived in good condition If not contact PANDUIT Technical Support Table 3 PANDUIT Corporation Contact Information PANDUIT Technical S...

Страница 11: ...green and yellow striped grounding strap to the panel via the unthreaded hole nearest the power connector Next install the panel into a grounded rack using the appropriate screw set provided to ensure...

Страница 12: ...chain fashion as shown Once all of the connections are made the DPoE Element Manager or another Network Manager will be able to communicate with all the panels over this daisy chain of connections Se...

Страница 13: ...NICATION LINE HAS BEEN DISCONNECTED AT THE NETWORK INTERFACE NOTE Never install wiring in a slot previously used for a larger gauge wire 10 Using the recommended punchdown tool PANDUIT part number PDT...

Страница 14: ...e power harness wires to the supply wires A crimping tool such as the PANDUIT part number CT 100 may be used The provided butt splices PANDUIT part number BSV14X support 14 16 AWG solid or stranded wi...

Страница 15: ...tatus LED above the IN management port will stay amber and the network status LED above the OUT management port will turn off This indicates that the panel is actively requesting address information f...

Страница 16: ...andards Also try to connect the device to another port to see if it powers on 4 The port Administration Control setting is set to OFF in the DPoE Element Manager The DPoE Element Manager must be used...

Страница 17: ...ption Status of Power Ports Off Off No Power is being supplied to the panel Power is NOT being delivered to the ports on the panel Green Flashing System operating normally Power may be delivered down...

Страница 18: ...hould be checked to ensure proper wiring has been followed Power is NOT being delivered down this port on the panel Table 9 Network Status LED Indications LED Color Network LED Status Description Note...

Страница 19: ...ssor or equivalent RAM 128 MB of RAM 256 MB recommended Hard Disk Space 45 MB of available hard disk space Network Access 10 100 Ethernet card CD ROM Drive Software Operating System Any Windows Vista...

Страница 20: ...le Launch exe Once all required support software is installed the installation screen will be displayed For security purposes the network operator will then be given the opportunity to restrict the DP...

Страница 21: ...to anything IMPORTANT Directly connecting a PC to the panel will either require the PC to be setup as a DHCP Server or require the DPoE Power Patch Panel to be setup for static IP addressing The pane...

Страница 22: ...els Likewise configuration changes can be made at the network panel or port level The Tree View of the Network area provides a hierarchical display of each patch panel within the network using the con...

Страница 23: ...l time display indicates the communication status between the DPoE Element Manager and the DPoE Power Patch Panels By adding additional UserNames to the DPoE Element Manager the network operator can a...

Страница 24: ...an be used to collect this information during installation When installing multiple DPoE devices simultaneously it is very important to record the MAC address for each panel Since multiple panels will...

Страница 25: ...er and the DPoE Power Patch Panels For security reasons these fields should be changed from their defaults Care should be taken however as the SNMP Community fields are case sensitive and will read in...

Страница 26: ...Power Patch Panel information will be populated in the DPoE Element Manager the Start button will initiate the Discover capability TIP In addition to the Discover capability the DPoE Element Manager...

Страница 27: ...ring its specific attributes into the DPoE Element Manager is an integral part of the provisioning activity Loading this information into the DPoE Element Manager enables it as well as Network Managem...

Страница 28: ...ay be a problem with the network connection itself The DPoE Element Manager reflects physical location information and power status based on the last time this information was refreshed In order to wo...

Страница 29: ...used to associate the discovered device with the information contained on the installation worksheet and the Panel Attributes can now be entered 6 Double click on the row in the table containing the...

Страница 30: ...oE Power Patch Panel Fill out per the example shown on right Click the OK button and the Device Physical Location information will be added to the device attributes field 8 Once all of the desired inf...

Страница 31: ...intuitive physical location information that is stored in each panel The DPoE Element Manager makes it easy to administer the deployed network of DPoE Power Patch Panels When a specific panel is sele...

Страница 32: ...set for this device This screen cannot be used to modify the configuration SNMP information The SNMP configuration can be edited selecting the Edit Panel Info button on the right side tool bar Edit Pa...

Страница 33: ...ple port 5 and the selected port will highlight with a flashing yellow indicator You will receive a dialog box on screen stating that the EMS is obtaining the latest information for the selected port...

Страница 34: ...e Rack Space Position field refer to Provisioning the Panel for more information Once these values are set in the DPoE Element Manager this information will be transmitted and stored in the DPoE Power...

Страница 35: ...ct the number of times a SNMP message retry occurs prior to receiving this Timeout error message The SNMP Retry function enables a choice of the amount of times the SNMP message is retried Once a devi...

Страница 36: ...one panel to another The Copy Panel and Paste Panel options under the Tools pull down menu provide an easy mechanism to perform this task Once a panel is highlighted in the Tree View of the Network a...

Страница 37: ...nto new units prior to configuration A dialog box will appear allowing device information to be exported for All Devices Devices that are in the Selected Rack Room or for the Selected Device The Refre...

Страница 38: ...atabase in memory is erased Restoring Device and Port Information The Import function allows retrieval of saved device and port data that has been previously extracted and saved to a file using the Ex...

Страница 39: ...device If a device is selected incorrectly it is possible to overwrite a 24 port configuration information into an 8 port device only the data representing the first 8 ports will be used Conversely a...

Страница 40: ...will bring up the configuration information for that individual port This is the same screen that will appear by double clicking an individual port on the Visual Display of the Front Panel portion on...

Страница 41: ...ort Screen Clicking on the Edit button will bring up a screen to edit individual ports on a DPoE Power Patch Panel If the network operator were simultaneously configuring multiple ports the Multiple P...

Страница 42: ...r a closed circuit condition and will not apply power until a load is detected across the circuit In Forced mode the device port will deliver power without performing a detection classification If not...

Страница 43: ...tial listing of all messages received by the DPoE Element Manager displaying them in a first in first out manner That is the most recently received messages are listed at the top of the window and the...

Страница 44: ...C addresses Panel name or range of panel names Port number or range of port numbers Specific message types Export Log By clicking on the Export Log button the operator is given the option of exporting...

Страница 45: ...the racks in a panel or a single panel within a rack By using the E mail mechanism the network operator can assign specific e mail addresses to be notified of network events For example the DPoE Elem...

Страница 46: ...anel of the E mail Settings the right panel is used to select which message categories will be sent to that e mail address refer to DPoE Element Manager Log Messages for more information on each of th...

Страница 47: ...User Manual Part Number PN378E 47 Panel level searches can be conducted by any combination of MAC address Panel Name Rack Name Rack Space Location Hardware Version IP Address Physical Location Power S...

Страница 48: ...378E 48 Port level searches can be conducted by any combination of Port Number PD Type Work Area Location Administration Control Detection Status Power Priority Power Classification Legacy Control NOT...

Страница 49: ...Device Power Above Threshold Major The power consumption at the device has risen above the Power Warning Threshold Device Power Below Threshold Major The power consumption at the device has fallen be...

Страница 50: ...panels in the racks in the same fashion as they are wired in the network racks Either the rack slots are numbered from with the highest rack positions at the top Descending or the highest rack positio...

Страница 51: ...st point to the directory where the new DPoE product file is stored 3 The Update Firmware under the option Tools pull down menu opens a window that identifies the IP address device type and device nam...

Страница 52: ...Ethernet Switch Initialization 00 01 seconds Amber Solid DHCP Initialization 01 100 seconds Green Blink DHCP complete Red rapid Blink Green Blink Image transfer and update in progress 5 7 minutes Red...

Страница 53: ...PWRR1250 1250 watt rectifier for use in the DPOEPWRCU chassis CORD A Power cord for Australia CORD E Power cord for Europe CORD S15 Power cord for North America CORD J15 Power cord for Japan CORD UPWR...

Страница 54: ...S 30 The PAN TY S are used to secure the shielded cable to the rear shield and secure the shield Verify the above contents arrived in good condition If not contact PANDUIT Technical Support Table 15 P...

Страница 55: ...at the planned rack position 4 Record the rack space position on the Installation Worksheet 5 Prepare the shielded cables for termination using the figures appropriate for the type of cable used Cauti...

Страница 56: ...sponding to a EIA TIA 568A or EIA TIA 568B configured data pairs wiring sequence must be used Table 16 Color Coded Wire Positions for 802 3af 2003 Compliant Devices Pin Outs EIA TIA 568A Pin Outs EIA...

Страница 57: ...TE GREEN 1 WHITE ORANGE 2 GREEN 2 ORANGE 3 WHITE ORANGE 3 WHITE GREEN 6 ORANGE 6 GREEN 7 WHITE BLUE 7 WHITE BLUE 8 BLUE 8 BLUE 7 For best performance the cable pair twists should be maintained as clos...

Страница 58: ...be able to communicate with all the panels over this daisy chain of connections See Panel Provisioning the for more information Power Requirements 10 If the panel is being powered by an individual pow...

Страница 59: ...cal Support for more information about connecting the redundant B Feed Power 13 Lightly tug on the butt spliced connections to verify that the butt splices are secure 14 Plug the connector into the ba...

Страница 60: ...s configured for Dynamic Host Control Protocol DHCP address assignment and a cable is NOT connected to the IN management port on the rear of the panel the panel status LED will blink green If the DPoE...

Страница 61: ...om the front of the unit If the panel were set to static IP addressing rather than DHCP the network status LED above the IN management port will immediately turn green If the panel were set to static...

Страница 62: ...et IEEE 802af specifications Typical per port power output IEEE 802 3af 2003 compliant power 15 4 watts port 46VOUTDC 350mA Maximum overall power consumption 490 Watts 57VINDC 8 6 A Mounting Option Mo...

Страница 63: ...cal and Electronic Engineers IP Internet Protocol LED Light Emitting Diode MAC Media Access Control MHz Megahertz NMS Network Management System o d Outside Diameter PC Personal Computer PD Powered Dev...

Страница 64: ...roducts freetools index aspx TFTPServer 3Com Freeware ftp ftp 3com com pub utilbin win32 3cs117 zip Weird Solutions Shareware http www weirdsolutions com weirdSolutions files products desktopSoftware...

Страница 65: ...PANDUIT DPoE Power Patch Panel User Manual Part Number PN378E 65 Click Yes Click Next...

Страница 66: ...Patch Panel User Manual Part Number PN378E 66 Click Finish Now run the program Move your mouse to the Start Menu lower left corner Start Menu All Programs Solar Winds Free Tools TFTP Server Go to the...

Страница 67: ...configured correctly After the download works you will see something like this on the screen that shows the file transfer Note If you are using a TFTP server from another vendor they may have some us...