2.11 Configure settings for RS485 [RS485]
S11x2
Configure settings related to RS485 communication in the “RS485” page.
[Baud rate]
Select the baud rate for RS485 transmission from the following:
2400bps/ 4800bps/ 9600bps/ 19200bps/ 38400bps
•
Default:
19200bps
[Data bit]
Select the data bit from 7 bit or 8 bit.
•
Default:
8bit
[Parity check]
Select from the following to determine whether or not to perform the parity check.
None/Odd/Even
•
Default:
None
[Protocol]
Select the RS485 control command from the following:
Pelco-D/Pelco-P/Custom
•
Default:
Pelco-D
[Unit address]
On RS485 lines that are linked together, an address is allotted to each connected device in order to send
commands to a specific connected device. Ensure that there is no duplication in the address of connected
devices. The setting range for the unit address depends on the protocol which you are using. The characters
which can be used are [0-9, 1-z, A-Z].
•
Default:
01
[RS485 operation screen]
Determine whether or not to display items related to RS485 transmission on the “Live” page.
•
On(pan/tilt head):
Displays a screen that uses RS485 transmission to control the pan/tilt head.
204
Operating Instructions
2 Settings
Содержание WV-S2500 Series
Страница 11: ...max 5fps When Off is selected for Stream transmission max 30fps Operating Instructions 11 1 Operations ...
Страница 157: ...2 9 2 1 Configure the settings related to sending E mails Operating Instructions 157 2 Settings ...
Страница 177: ...2 Click Install Certificate 3 Click Next displayed in Certificate Import Wizard Operating Instructions 177 2 Settings ...
Страница 219: ... When using a firewall including software allow access to all UDP ports Operating Instructions 219 3 Others ...
Страница 235: ...Operating Instructions 235 Notes ...