Bad Examples and Good Examples in Installation
Urban Multi Inverter “MX1” Series
75
7.5
Example 5:
Excessive noise due to incorrect angling of Line branch pipes
Situation
The noise of the refrigerant flow during defrosing is excessive.
Source of Problem
and Remedial
Action
The angle of the fittings was incorrect and needed to be rectified as shown in the following figure.
1. Line branch pipes
The Line branch pipes should be installed such that branches meet the main pipe either horizontally or
vertically at an angle of exactly 90 degrees.
2. Header branch pipes
The Header branch pipes is a lateral flow pipe and should be fitted so as to allow horizontal branch
fittings. (Vertical or sloping fitting is not permissible.)
Main Points
Reasons for using refrigerant branch kit
Fittings of Line branch pipes or Header branch pipes which are not carried out in strict accordance with
the principles outlined here may result in complaints relating, for example, to “poor performance” of the
system or “noisy refrigerant flow”. (To prevent unbalance flow or oil shortage)
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...