5. Caution for
Refrigerant Leaks
5.1
Caution for Refrigerant Leaks
5.1.1
Introduction
(Points to note in connection with refrigerant leaks)
The installer and system specialist shall secure safety against leakage according to local regulations or
standards. The following standards may be applicable if local regulations are not available.
The Urban Multi, like most other air conditioning systems, uses “R-22” as its refrigerant.“R-22” itself is an
entirely safe non-toxic,non-combustible refrigerant but care must nevertheless be taken to ensure that the
air conditioning facilities are installed in a room which is sufficiently large to avoid a *dangerous
concentration of refrigerant gas in the unlikely event of a serious leak in the system. The KHK (High
Pressure Gas Protection Association, in Japan) has established its own standard in respect of refrigerant
gas concentrations for inclusion with the general standards covering refrigeration and air conditioning
facilities.
5.1.2
Maximum Concentration Level
Dangerous concentration
Dangerous concentration means the maximum concentration of CFC gas which can be dealt quickly and
with without damage to the person in the case of a leak of refrigerant into the air. The unit of measurement
of the dangerous concentration is kg/m³ (the weight in kg of CFC gas in 1m³ of air) for ease of calculation.
Dangerous concentration of R-22: 0.3 kg/m³
(KHK facility standard: S0010)
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant
is heavier than air.
direction of the refrigerant flow
room where refrigerant leak
has occurred (outflow of all the
refrigerant from the system)
3PA63729-7Q
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...