2WAY VRF SYSTEM
Control Functions
1
- 40
1
2
3
4
5
6
7
8
9
12. Other Functions
(1) Auto Change over Cooling/Heating Function
It is possible to select auto change over cooling/heating mode in each remote controller even in 2WAY VRF
system.
The system changes to cooling or heating operation according to number of thermostat ON mode.
The system selects the mode that has more number of units with thermostat ON.
(It is impossible to perform the simultaneous cooling/heating operation.)
The system judges whether to switch the mode in XX minutes intervals.
Case 1
Number of thermostat ON indoor units in cooling mode > Number of thermostat ON indoor units in heating mode
→ system selects cooling mode
The heating indoor units will be forced to thermostat OFF.
Case 2
Number of thermostat ON indoor units in cooling mode < Number of thermostat ON indoor units in heating mode
→ system selects heating mode
The cooling indoor units will be forced to thermostat OFF.
* “XX” is able to be set in EEPROM on the outdoor unit’s PCB.
EEPROM setting in main outdoor unit
CODE: 27
Setting No.
XX
0
Invalid
(factory preset mode)
30
30
40
40
50
50
60
60
90
90
120
120
180
180
240
240