2WAY VRF SYSTEM
Control Functions
1
- 37
1
2
3
4
5
6
7
8
9
11. Backup Operation
3WAY SYSTEM
Control Functions
12. Backup Operation
Alarm list 2 (Backup operation continues as long as the problems are not solved.)
Alarm display
DISCH1 thermistor at the discharge of 1st compressor reading is abnormal
DISCH2 thermistor at the discharge of 2nd compressor reading is abnormal
EXG1 thermistor at the gas side of 1st heat exchanger of the outdoor unit
has failure (EXG1)
EXL1 thermistor at the liquid side of 1st heat exchanger of the outdoor unit
has failure (EXL1)
TO thermistor for outdoor ambient air temperature has failure (TO)
B
SCT thermistor at the suction refrigerant of compressors has failure (SCT)
SCG thermistor at the outlet of subcooling heat exchanger in outdoor unit
has failure (SCG)
High pressure sensor of the outdoor unit has failure (HPS)
B
B
B
B
B
B
B
F05
F04
F06
F08
F07
F12
F16
F14
Low pressure sensor of the outdoor unit has failure (LPS)
EXG2 thermistor at the gas side of 2nd heat exchanger of the outdoor unit
has failure (EXG2)
EXL2 thermistor at the liquid side of 2nd heat exchanger of the outdoor unit
has failure (EXL2)
DISCH1 thermistor at the discharge of 1st compressor is disconnected,
shorted or misplaced (DISCH1)
OIL1 thermistor for the oil of 1st compressor has failure (OIL1)
DISCH2 thermistor at the discharge of 2nd compressor is disconnected,
shorted or misplaced (DISCH2)
OIL2 thermistor for the oil of 2nd compressor has failure (OIL2)
B
B
B
B
B
B
B
F23
F17
F24
H08
H05
H27
H15
1st compressor discharge temperature too high
2nd compressor discharge temperature too high
B
B
P17
P03
1-2. Start of automatic backup operation
If the above alarms occur, the alarm is displayed on the remote controller, etc.
Pressing the remote controller button again starts automatic backup mode.
1-3. Backup operation information display
* Backup operation caused by an alarm listed in “alarm list 2” will finish automatically after 24 hours if the same
alarm does not occur again for 24 hours.
A : When there is one outdoor unit in the system, only compressor that has sensor failure stops.
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
B : When there is one outdoor unit in the system, the backup operation does not work.
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
If a wired remote controller is present,
display blinks during operation.