2WAY VRF SYSTEM
Control Functions
1
- 36
1
2
3
4
5
6
7
8
9
11. Backup Operation
3WAY SYSTEM
Control Functions
12. Backup Operation
This system includes a function for automatic backup operation.
An alarm is displayed on the remote controller to inform the user that a failure has occurred.
When the following alarm occurs, automatic backup operation is engaged.
Automatic backup operation is not engaged in cases of serious alarm such as communications alarms, etc.
A : When there is one outdoor unit in the system, only compressor that has sensor failure stops.
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
B :
NOTE :
After automatic backup operation caused by alarm listed in alarm list 1, it will not be canceled automatically
when the repair of the failed outdoor unit is completed.
Automatic backup mode will be canceled only when the power on all outdoor unit is reset.
Therefore, after repair work is completed, be sure to check whether or not automatic backup mode has been
canceled.
When there is one outdoor unit in the system, the backup operation does not work.
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
(1) Automatic Backup Operation
1-1. Alarms that result in automatic backup operation
Alarm list 1 (Backup operation continues unless power supply of all outdoor units is turned off.)
Alarm display
Overcurrent in 1st compressor
Overcurrent in 2nd compressor
Current sensor for the 1st compressor is disconnected or shorted
Current sensor for the 2nd compressor is disconnected or shorted
Low on oil or the oil recovery circuit has restriction
A
Overcurrent of 1st compressor on the secondary side of inverter circuit,
or inverter failed to syncronize with rotation
Overcurrent of 2nd compressor on the secondary side of inverter circuit,
or inverter failed to syncronize with rotation
Inverter for 1st compressor failed to start or failed to syncronize with
rotation
A
A
A
B
A
A
A
H11
H01
H03
H07
HIC for 1st compressor has failure
Overcurrent or overheat of HIC
A
H31
HIC for 2nd compressor has failure
Overcurrent or overheat of HIC
A
H21
H13
P16
P29
Inverter for 2nd compressor failed to start or failed to syncronize with
rotation
A
P19
Fan motor or inverter drive of outdoor unit has failure
B
P22
P26