10. Upper Current Limitation Mode (Demand control)
3WAY SYSTEM
Control Functions
10. Upper Current Limitation Mode (Demand control)
EEPROM setting in main outdoor unit
CODE: 1A
Setting No.
XX
0
0
40
40
45
45
Control
Contact 1
Upper current limitation setting
Contact 2
No control (Operates to maximum capacity)
Operates to XX% of the upper limit for the rated current.
Operates to YY% of the upper limit for the rated current.
Forced thermostat OFF setting
There are 2 types of control; demand control and infinity limit in the upper current limitation mode.
Either of them is controlled by the lower current limitation.
Serial-parallel I/O must be connected in order to perform demand control.
The below input is received by serial-parallel I/O, and demand control is performed.
The demand values can be set as needed with serial-parallel I/O.
* The rated current indicates the current value that is listed in the catalog or similar material.
* XX and YY are able to set in EEPROM of main outdoor unit.
: Input present
: Input not present
(1) Demand Control
-1
No control
130
130
CODE: 1B
Setting No.
YY
0
0
40
40
45
45
Interval of “5”
100
100 (factory preset mode)
-1
No control
130
130
Interval of “5”
70
70 (factory preset mode)
72
96
120
144
7.2 A
9.8 A
12.7 A
16.5 A
7.9 A
10.0 A
13.5 A
16.8 A
Cooling mode
Type of outdoor unit
Heating mode
The standard value of the limit current is listed in the table below.
U-72ME2U94 / U-96ME2U94 / U-120ME2U94 / U-144ME2U94
72
96
120
144
15.6 A
20.9 A
26.5 A
35.7 A
16.8 A
22.2 A
28.9 A
37.5 A
Cooling mode
Type of outdoor unit
Heating mode
U-72ME2U9 / U-96ME2U9 / U-120ME2U9 / U-144ME2U9