2WAY VRF SYSTEM
Trouble Diagnosis
3. 2WAY Alarm Codes
P22 Alarm (U-72ME2U9 / U-96ME2U9 / U-120ME2U9 / U-144ME2U9)
Alarm code
Alarm meaning
Alarm conditions
Probable cause
P22
Fan motor or inverter drive of outdoor unit has failure.
Fan motor start failure, fan motor Hall IC input failure
Possible causes are a Hall IC input circuit failure and a Fan PCB failure.
Check
Check the fan motor wiring, the Hall IC wiring, and the connector connections.
If the wiring and connectors are normal, then measure the resistance between fan HIC power (P)
and ground (N) with the tester.
If there is a short-circuit, there is an HIC malfunction.
Correction
(1) If there is a fan HIC failure or circuit failure, replace the FAN PCB.
(2) If the fan motor is locked, replace the fan motor.
Example
Notes
If the fan does not start, the below corrections may be effective.
—
Turn OFF the power, and check the continuity of “P” and “N” on the FAN PCB.
FAN PCB
(A747844)
P
N
P20 Alarm
Alarm code
P20
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
Example
Notes
Too high load in refrigerant circuit.
The high pressure increase is not rapid but the alarm occurs when the horsepower down does
not meet the anticipated time.
(1) Forgot to open the valve.
(2) Operation failure of mechanical valve
(3) Idle away of outdoor fan
Check the valve, mechanical valve and outdoor fan.
—
—
—