2WAY VRF SYSTEM
Trouble Diagnosis
3. 2WAY Alarm Codes
P05, P15 Alarm
Alarm code
P05, P15
Alarm meaning
P05 : Open phase in power input is detected at HIC for 1st compressor.
P15 : Open phase in power input is detected at HIC for 2nd compressor.
Alarm conditions
This alarm occurs when open phase detected in the L1-L2-L3 phases.
Probable cause
Open phase in the L1-L2-L3 phases
Check
Check the wiring at the power terminal board.
Correction
Switch the phases and reinsert. Check if the result is OK.
P14 Alarm
Alarm code
P14
Alarm meaning
Input detected at EXCT terminal on indoor PCB for refrigerant detector.
Alarm conditions
(1) It is judged an error whenever the outdoor unit receives the signal “O
2
Alarm Generated”
from the indoor unit.
(2) With the indoor unit's EEPROM setting (item code 0B) set to 0001, the EXCT input was
shorted.
Probable cause
—
Check
(1) System configuration
1-1 Is an O
2
sensor being used?
If “Yes”, see “3-1”.
If “No”, see “2-1”.
(2) Indoor EEPROM setting
2-1 Is the EEPROM setting, item code 0B, on the indoor control board set to 0001?
If “Yes”, change the setting of item code 0B to
“0000” from “0001”.
If “No”, see “3-1”.
(3) Indoor Unit Control board
3-1 Is the alarm triggered if the EXCT socket (wire) is disconnected, and the power is reset?
If “Yes”, see “3-3”.
If “No”, see “3-2 ”.
3-2 Since there is no error, see what happens.
3-3 Indoor Control board defective
→
replace board
Example
—
Notes
—
P16, P26 Alarm
Alarm code
P16, P26
Alarm meaning
P16 : Overcurrent of 1st compressor on the secondary side of inverter circuit, or inverter failed to
syncronize with rotation.
P26 : Overcurrent of 2nd compressor on the secondary side of inverter circuit, or inverter failed to
syncronize with rotation.
Alarm conditions
This alarm occurs when current trouble or current detection
trouble occur (when trouble judgement current is detected
in the secondary current).
* Changed to output error by current regardless of the inverter
frequency.
When more than the current values shown in the table are
instantly detected in the secondary current.
Secondary current
Model name
U-72ME2U9
U-96ME2U9 U-120ME2U9 U-144ME2U9
Current (A)
30.0
44.0
30.0
30.0
Model name
U-72ME2U94 U-96ME2U94 U-120ME2U94 U-144ME2U94
Current (A)
16.6
23.0
16.6
16.6
Probable cause
There is a strong possibility of a compressor failure.
An alarm occurs for current detection trouble when it is judged that no current is flowing after
start (DCCT is damaged). In this case, the cause is a DCCT failure.
Check
Check the power wiring and connector wiring.
Correction
It is possible to resolve this trouble by limiting the maximum frequency.
Example
—
Notes
—
Inverter compressor
HIC PCB
U
V
W
Secondary
current