5
- 20
1
2
3
4
5
6
7
8
9
2WAY VRF SYSTEM
Trouble Diagnosis
3. 2WAY Alarm Codes
H08, H27 Alarm
Alarm code
H08, H27
Alarm meaning
H08 : OIL1 thermistor for the oil of 1st compressor has failure. (OIL1)
H27 : OIL2 thermistor for the oil of 2nd compressor has failure. (OIL2)
Alarm conditions
This alarm occurs when a connector connection (pins 1 and 2 for 1st compressor, and pins 4
and 5 for 2nd compressor) is open.
Probable cause
Disconnected connector
Check
Check that the connector is securely connected.
Correction
(1) Connect the connector.
(2) Correct the connection at connector pins 1 and 2, or pins 3 and 4.
Example
—
Notes
—
SM830237-07_北米向け2WAY_VRF.indb 20
18/06/18 18:50:11