2WAY VRF SYSTEM
Trouble Diagnosis
3. 2WAY Alarm Codes
F08 Alarm
Alarm code
F08
Alarm meaning
TO thermistor for outdoor ambient air temperature has failure. (TO)
Alarm conditions
(1) Short circuit (A/D step is 10 steps or less.)
(2) Open circuit (A/D step is 1014 steps or more.)
Probable cause
(1) Sensor malfunction (including connector)
(2) The Outdoor Unit Control PCB malfunction
Check
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
—
Example
—
Notes
—
F12 Alarm
Alarm code
F12
Alarm meaning
SCT thermistor at the suction refrigerant of compressors has failure. (SCT)
Alarm conditions
(1) Short circuit (A/D step is 10 steps or less.)
(2) Open circuit (A/D step is 1014 steps or more.)
Probable cause
(1) Sensor malfunction (including connector)
(2) The Outdoor Unit Control PCB malfunction
Check
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
—
Example
—
Notes
—
F14 Alarm
Alarm code
F14
Alarm meaning
SCG thermistor at the outlet of subcooling heat exchanger in outdoor unit has failure. (SCG)
Alarm conditions
(1) Short circuit (A/D step is 10 steps or less.)
(2) Open circuit (A/D step is 1014 steps or more.)
Probable cause
(1) Sensor malfunction (including connector)
(2) The Outdoor Unit Control PCB malfunction
Check
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
—
Example
—
Notes
—