2WAY VRF SYSTEM
Trouble Diagnosis
3. 2WAY Alarm Codes
Alarm code
Alarm meaning
Page
P03
1st compressor discharge temperature too high.
5
-25
P04
Protection device activated. High pressure switch (63PH, 63PH1 or 63PH2) or compressor
thermal protector (49C1 / 49C2).
5
-26
P05
Open phase in power input is detected at HIC for 1st compressor.
5
-27
P15
Open phase in power input is detected at HIC for 2nd compressor.
5
-27
P14
Input detected at EXCT terminal on indoor PCB for refrigerant detector.
5
-27
P16
Overcurrent of 1st compressor on the secondary side of inverter circuit, or inverter failed to
syncronize with rotation.
5
-27
P26
Overcurrent of 2nd compressor on the secondary side of inverter circuit, or inverter failed to
syncronize with rotation.
5
-27
P17
2nd compressor discharge temperature too high.
5
-25
P20
Too high load in refrigerant circuit.
5
-28
P22
Fan motor or inverter drive of outdoor unit has failure.
5
-28,
5
-29
P29
Inverter for 1st compressor failed to start or failed to syncronize with rotation.
5
-29
P19
Inverter for 2nd compressor failed to start or failed to syncronize with rotation.
5
-29
Blinking Inspection Display on the remote controller
5
-30