1. Contents of Remote Controller
Switch Alarm Display
2WAY VRF SYSTEM
Trouble Diagnosis
ON: Blinking:
OFF:
Possible cause of malfunction
Wired
remote
control
display
Wireless
remote controller
receiver display
Operation
Timer
Standby for heating
Serial communi-
cation errors
Mis-setting
Remote controller is detecting
error signal from indoor unit.
Indoor unit does not respond to remote controller.
<E01>
The remote controller is having error in sending serial
communication signal.
<E02>
Controller does not respond to indoor unit.
<<E03>>
Indoor unit is detecting error
signal from outdoor unit.
Outdoor unit does not respond to indoor unit.
E04
Outdoor unit is detecting error
signal from indoor unit.
Some indoor units does not respond to outdoor unit.
E06
Improper setting
Indoor unit address is dupulicating.
E08
Two or more remote controllers are set as main on R1-R2 link. <<E09>>
Improper setting
Auto Address failed to start.
E12
Indoor unit communication
error of group control wiring
No response from sub indoor to the main indoor unit in group
control wiring.
E18
During auto. address setting,
number of connected units
does not correspond to
number set.
Fewer indoor units are found in Auto Addressing than the
setting on outdoor PCB.
E15
More indoor units are found in Auto Addressing than the
setting on outdoor PCB.
E16
No indoor unit responded in Auto Addressing.
E20
No response from sub outdoor unit.
E24
The outdoor unit address is duplicating.
E25
The number of responding outdoor units does not match with
the setting on the main outdoor unit.
E26
No response from main outdoor unit.
E29
The outdoor unit is having error in sending serial
communication signal on main-sub communication line.
E30
Error in communication inside outdoor unit control box.
E31
Improper setting
Indoor unit model does not match with the outdoor unit model.
(Multi-split/mini-split)
<<L02>>
Two or more indoor units are set as main in group control.
<L03>
Two or more indoor units are set as priority indoor unit.
L05
Two or more indoor units are set as priority indoor unit.
L06
Group control wiring is detected for indoor unit set as
individual control.
L07
Indoor unit address is not set.
L08
Capacity setting of indoor unit is not correct.
<<L09>>
Duplicate system address setting on outdoor units.
L04
Capacity setting of outdoor unit is not correct.
L10
Model mismatch between outdoor units in one refrigerant
circuit.
L17
Reversing valve or solenoid valve failure.
L18
Thermistor fault Indoor unit
E1 thermistor on liquid side of indoor heat exchanger has
failure. (E1)
<<F01>>
Indoor unit set as single split. (E2)
<<F02>>
E3 thermistor on gas side of indoor heat exchanger has
failure. (E3)
<<F03>>
TA thermistor for intake air temperature (room temperature) of
the indoor unit has failure. (TA)
<<F10>>
BL thermistor for supply air temperature of the indoor unit has
failure. (BL)
<<F11>>
Outdoor unit
DISCH1 thermistor at the discharge of 1st compressor
reading is abnormal.
F04
DISCH2 thermistor at the discharge of 2nd compressor
reading is abnormal.
F05
EXG1 thermistor at the gas side of 1st heat exchanger of the
outdoor unit has failure. (EXG1)
F06
EXL1 thermistor at the liquid side of 1st heat exchanger of the
outdoor unit has failure. (EXL1)
F07
TO thermistor for outdoor ambient air temperature has failure.
(TO)
F08
Continued
Operating and
timer lamps blinking
alternately
Operating and
timer lamps blinking
alternately
Operating and heating
ready lamps blinking
simultaneously
Operating and heating
ready lamps blinking
simultaneously
Heating ready lamp
blinking
Heating ready lamp
blinking
Operating lamp
blinking
Operating lamp
blinking