2WAY VRF SYSTEM
Remote Controller Functions
4
- 31
1
2
3
4
5
6
7
8
9
3. Remote Controller Servicing Functions
<Procedure of CZ-RTC4>
1. Press and hold the
button for 4 seconds or
Operates the unit with the thermostat forced ON.
longer.
2. “
” appears on the remote controller LCD
display.
3. Press the
button to start the test run.
The outdoor units will not operate for
approximately 3 minutes after the power
is turned ON and after operation is stopped.
A
°
°
4. Press the button to return to normal remote controller display.
•
The temperature cannot be adjusted in Test Run mode.
(This mode places a heavy load on the machines.
Therefore use it only when performing the test run.)
•
The test run can be performed using the HEAT, COOL,
or FAN operation modes.
•
To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after
60 minutes.
•
The operation is possible even if the cassette-type ceiling panel has not been installed.
(“P09” display does not occur.)
•
If correct operation is not possible, an error code is
displayed on the remote controller LCD display.
3
1, 4
2