2WAY VRF SYSTEM
Remote Controller Functions
4
- 12
1
2
3
4
5
6
7
8
9
2. Detailed Settings Function
Item code
Item
Setting data
No.
Description
Automatic drain pump
operation
0000 No forced operation
0001 Forced operation for 1 minute
0060 Continuous operation
Ventilation fan operation
0000 None
0001 Ventilation fan operated by remote controller.
Wired remote controller
sensor
0000 Not used. (Body sensor is used.)
0001 Remote control sensor is used.
Temperature display
setting
0000 °C
0001 °F
“Operation change
control in progress”
display
0000 Normal (displayed)
0001 Not displayed
OFF reminder function
for when weekly timer is
used
0000 None
0001 Only stop time setting is enabled.
Humidifier / emergency
heater output setting
0000 Humidifier output
0002 Emergency heater output
Discharge temperature
control
0000 Discharge temperature control OFF
0001 Discharge temperature control ON
Heat exchanger
temperature for cold air
discharge
(Heat exchanger control
point for control to
prevent cold air)
0013 Control temperature 55°F
0014 Control temperature 57°F
0025 Control temperature 77°F
0026 Control temperature 78°F
Fan output switching
0000 Output linked with fan. (ON when indoor unit fan is operating.)
0001 Fan mode operation output
Drain pump delayed
stop time
0000 No delayed stop
0001 1 sec. delayed stop
Except
Indoor unit
Type
F2, U2, T2
1 min. delayed stop
Indoor unit
Type
F2, U2, T2
0002 2 sec. delayed stop
2 min. delayed stop
0058 58 sec. delayed stop
58 min. delayed stop
0059 59 sec. delayed stop
59 min. delayed stop
0060 60 sec. delayed stop
60 min. delayed stop
Humidifier setting
0000 Humidifier output OFF. Drain pump stopped.
0001 Humidifier output ON. Drain pump operates.
0002
Humidifier output ON. Drain pump operates for 1 minute when total humidifier
operating time reaches 60 minutes.
0003 Humidifier output ON. Drain pump stopped.
Flap operation mode
0000 Standard setting
0001 Draft reduction mode (Flap lower-limit position is shifted upwards.)
Flap swing mode
0000 Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)
0001 Normal mode
0002 Draft reduction mode (Flap swing lower-limit position is upwards.)