SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
156/184
Appendix 2.3.
FB error code (o_uErrId) list
The following is a list of error codes output by the FBs in this FB library to Error Code (o_uErrId).
Error Code
Hexadecimal
(Decimal)
Description
Meaning
In
pu
t v
al
ue er
ro
r r
el
at
ed
er
ro
r co
des
100
(256)
The Station No. (i_uStationNo) is outside the valid
range
For CC-Link master/local module
Set the Station No. (i_uStationNo) to a value from 1
to 64.
For CC-Link IE Field master/local module
Set the Station No. (i_uStationNo) to a value from 1
to 120.
101
(257)
The information derived from the input Start I/O
No.(i_uStartIONo) and the Station No.
(i_uStationNo) is not SC-HG1-C or SC-HG1-CEF.
Check if the Start I/O No.(i_uStartIONo) and the
Station No. (i_uStationNo) settings correctly indicate
the target communication unit.
102
(258)
CC-Link IE Field Flag (i_bIeFieldFlag) is ON and
Execution Command (i_bEN) is ON
Turn ON Execution Command (i_bEN) with
CC-Link IE Field Flag (i_bIeFieldFlag) OFF.
103
(259)
Response Data (i_uResponseData) is outside the
valid range
Specify a value within the valid range.
104
(260)
Set to a controller where Set Controller
(i_uSetController) is set to 0 or does not exist
Make the value of Set Controller (i_uSetController)
greater than 0 or turn ON All Controller Set
(i_bAllSetRequest).
Check if the setting is not applied to a controller
beyond the maximum number of connected units.
Also, check if the 15th bit of Set Controller
(i_uSetController) is not ON.
105
(261)
Input Command (i_uCommand) is outside the valid
range
Enter the correct command.
106
(262)
Teaching Steps (i_uTeachStep) is outside the valid
range
Set Teaching Steps (i_uTeachStep) to a value not
greater than 2.
107
(263)
"1-point teaching" is selected and Shift Amount
(i_udShiftAmount) is outside the valid range
Selecting "1-point teaching" requires you to set Shift
Amount (i_udShiftAmount) to a value within the
valid range.
108
(264)
Input Signal (i_bInputSignal) is ON and Execution
Command (i_bEN) is ON
Turn OFF Input Signal (i_bInputSignal) and then turn
ON Execution Command (i_bEN)
109
(265)
Hold Setting (i_uHoldSetting) is outside the valid
range
Specify a value within the valid range.