4.4 Command List
WUME-SCHG1ETC-2
4-22
4.4.2 HG-T Series Command List
The following table shows the command parameters that are used to read and write controller
settings and statuses and to send operation commands to controllers.
For details, refer to the
“HG-T User’s Manual”
.
Attributes R: Read, W: Write, R/W: Read/Write
Command
Attribute
Name
Response/Setting parameter
HG-T
series
0x0001
R
Status/Error
When status is normal = 0
When error occurs = Error code
0x0002 to 0x0004
-
System reserved
Do not use.
0x0005
W
Controller reset
Reset the controller. (Master unit only)
0x0006
W
Initialization (RESET)
Return the settings to the factory default state.
Do not specify "0".
0x0007 to 0x000F
-
System reserved
Do not use.
0x0010
R
Judgment value (JUDGE.V)
Integer indicating minimum resolution units of
controller.
-1999999 to 1999999
0x0011
R
Normal measured value
(NORM.V)
Integer indicating minimum resolution units of
controller.
-1999999 to 1999999
0x0012
R
Calculated value (CALC)
Integer indicating minimum resolution units of
controller.
If a calculated value is not set, the judgment
value is output.
-1999999 to 1999999
0x0013
R
Sensor head measured value
(HEAD.V)
Integer indicating minimum resolution units of
controller.
-1999999 to 1999999
0x0014
R/W LOW set value (LO.SET)
Integer indicating minimum resolution units of
controller.
-1999999 to 1999999
0x0015
R/W HIGH set value (HI.SET)
Integer indicating minimum resolution units of
controller.
-1999999 to 1999999
0x0016 to 0x0017
-
System reserved
Do not use.
0x0018
R/W Hysteresis (HYSTER)
Integer indicating minimum resolution units of
controller.
0 to 1999999
0x0019
-
System reserved
Do not use.
0x001A
R/W Output operation (OUTPUT)
0: N.O.
1: N.C.
0x001B
-
System reserved
Do not use.
0x001C
R
Output state
bit0: External output 1 (0 = OFF / 1 = ON)
bit1: External output 2 (0 = OFF / 1 = ON)
bit2: External output 3 (0 = OFF / 1 = ON)
The high bit is “0”.
0x001D
R
Input state
bit0: External input 1 (0 = OFF / 1 = ON)
bit1: External input 2 (0 = OFF / 1 = ON)
bit2: External input 3 (0 = OFF / 1 = ON)
The high bit is “0”.
0x001E
W
Execute bank load (LOAD)
Bank numbers 1 to 3 are loaded
0x001F
W
Execute bank save (SAVE)
Bank numbers 1 to 3 are saved
0x0020
R/W Key lock (LOCK)
0: Key lock OFF
1: Key lock ON
0x0021
R/W Eco mode (ECO)
0: Eco mode OFF
1: Eco mode ON
Содержание SC-HG1-ETC
Страница 2: ...WUME SCHG1ETC 2 2 MEMO ...
Страница 14: ...WUME SCHG1ETC 2 1 8 MEMO ...
Страница 15: ...2 1 2 System Configuration 2 1 System Configuration of This Product 2 2 2 2 Compatible Devices 2 4 ...
Страница 20: ...WUME SCHG1ETC 2 2 6 MEMO ...
Страница 30: ...WUME SCHG1ETC 2 3 10 MEMO ...
Страница 80: ...WUME SCHG1ETC 2 4 50 MEMO ...
Страница 90: ...WUME SCLG2CEFP 2 5 10 MEMO ...
Страница 91: ...6 1 6 Specification and Dimensions 6 1 Specifications 6 2 6 2 Dimensions 6 3 ...
Страница 94: ...WUME SCHG1ETC 2 6 4 MEMO ...
Страница 95: ...7 1 7 Warranty 7 1 Important Information about Order and Use of This Product 7 2 ...
Страница 98: ...WUME SCHG1ETC 2 7 4 MEMO ...
Страница 101: ...9 1 9 Troubleshooting 9 1 Error Codes and Solutions 9 2 9 2 Solutions to Problems 9 4 ...
Страница 108: ...10 2 Sample Program WUME SCHG1ETC 2 10 4 10 2 Sample Program 1 2 3 4 5 6 ...
Страница 114: ... MEMO ...
Страница 115: ... MEMO ...