REFERENCE NO.

SM830243-00

Indoor Unit

Order No. SBPAC1509011CE

Air-to-Water INDOOR UNIT

Type

Indoor Unit Type

Rated Capacity

80

125

W1

Air-to-Water

S-80MW1E5

S-125MW1E5

SERVICE MANUAL & TEST RUN SERVICE MANUAL

Connectable outdoor unit lineup

This document is the Service Manual of the indoor unit.
For outdoor unit, refer to the Service Manual of the outdoor unit.

Type

Outdoor Unit Type

8 hp

10 hp

12 hp

14 hp

16 hp

MF2

3WAY VRF System

U-8MF2E8

U-10MF2E8

U-12MF2E8

U-14MF2E8

U-16MF2E8

September 2015

SM830243-00_欧州向け Air-to-Water(S-80MW1E5他)SM&TRSM.indb   1

2015/09/17   9:44:57

Содержание S-125MW1E5

Страница 1: ...ANUAL TEST RUN SERVICE MANUAL Connectable outdoor unit lineup This document is the Service Manual of the indoor unit For outdoor unit refer to the Service Manual of the outdoor unit Type Outdoor Unit Type 8 hp 10 hp 12 hp 14 hp 16 hp MF2 3WAY VRF System U 8MF2E8 U 10MF2E8 U 12MF2E8 U 14MF2E8 U 16MF2E8 September 2015 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 17 9 44 57 ...

Страница 2: ...f other components i e heater etc Overloaded wiring or wire connection points may cause electrical shock or fire CAUTION Do not apply excessive force to water pipes that may damage the pipes If water leakage occurs it will cause flooding and damage to other properties Carry out drainage piping as mentioned in installation instructions If drainage is not perfect water may enter the room and damage ...

Страница 3: ...t other than specified type It may cause product damage burst and injury etc Ventilate the room immediately in the event that is refrigerant gas leaks during the installation Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of toxic gas Keep all tubing runs as short as possible Apply refrigerant lubricant to the matching surfaces of the flare an...

Страница 4: ...efrigerant gas is leaking If the gas comes in contact with a burning stove gas water heater electric room heater or other heat source it can cause the generation of toxic gas Others WARNING CAUTION Do not sit or step on the unit you may fall down accidentally Do not touch the air inlet or the sharp aluminum fins of the outdoor unit You may get injured Do not stick any object into the FAN CASE You ...

Страница 5: ...Demand Signal Output Input Optional 2 11 15 Antifreeze Control 2 13 16 Troubleshooting Guide 2 14 Section 3 OUTDOOR UNIT REPAIR PROCEDURES 3 1 Refer to the Service Manual of Outdoor Unit Section 4 OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER 4 1 Refer to the Service Manual of Outdoor Unit Section 5 REMOTE CONTROLLER FUNCTIONS 5 1 1 Simple Settings Function 5 2 2 Detailed Settings Function 5 4 3 Deta...

Страница 6: ... MEMO v SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 6 2015 09 17 9 44 58 ...

Страница 7: ...1 1 Air to Water Indoor Unit 1 1 CONTROL FUNCTIONS Outdoor Unit Refer to the Service Manual of Outdoor Unit SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 15 11 43 08 ...

Страница 8: ... MEMO 1 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 11 43 08 ...

Страница 9: ...7 External Room Thermostat Control Optional 2 6 8 Water Pump Control 2 7 9 Flow Switch Control 2 7 10 Electric Heater Control 2 8 11 Sterilization Mode 2 8 12 2 Way Valve Control Optional 2 9 13 External Water Pump Optional 2 10 14 External Device Ready Demand Signal Output Input Optional 2 11 15 Antifreeze Control 2 13 16 Troubleshooting Guide 2 14 Contents SM830243 00_欧州向け Air to Water S 80MW1E5...

Страница 10: ... sensor 2 BL will detect the Water outlet temperature The thermostat is turned ON or OFF according to the following ΔTw ΔTw Heat Setting water temperature Water outlet temperature Thermo ON Conditions a and b a Heating mode or Tank mode b Δ Tw Heat Thermo ON margin Thermo OFF conditions a and b and c a Heating mode or Tank mode b Δ Tw Heat Thermo OFF margin c Not in Force Thermo ON 3 Cooling Mode ...

Страница 11: ...ostat 4 Tank Mode Operation ON OFF timing of Tank mode operation is basically the same as Heating mode The maximum Water outlet temperature is 65 C The Heat Pump operates at less than 45 C of the Water outlet temperature and will stop at 45 C After reaching 45 C the internal heater continues operating 3 Cooling Mode Operation 4 Tank Mode Operation SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM i...

Страница 12: ...perature of heating curve by the remote controller The shift range of the Water outlet temperature by the remote controller is 5 C 5 C The shifted temperature is displayed in the remote controller as setting temperature If the shifted temperature is more than the upper limit or less than the lower limit as shown below the shifted temperature is limited between the upper and lower limit Heating Cur...

Страница 13: ...ature in Heating mode Setting room temperature 5 C Heating mode Thermo ON conditions a and b a Δ Tr heat Difference of air conditioning b Δ Tw heat Thermo ON margin Thermo OFF conditions a or b and c a Δ Tr heat 1 Difference of air conditioning b Δ Tw heat Thermo OFF margin c Not in Force Thermo ON Cooling mode Thermo ON conditions a and b and e or c and d a Δ Tr cool Difference of air conditionin...

Страница 14: ...ouch panel Siemens RAA20 Analog Connection of external room thermostat Wire Connection and thermostat characteristic of Siemens REV200 RAA20 Setting Heating mode Cooling mode L L1 Y1 motions L L1 Y1 motions Setting Room Temp Actual Temp Open Circuit OFF Open Circuit ON Setting Room Temp Actual Temp Short Circuit ON Short Circuit OFF Terminal board No 10 12 Example 7 External Room Thermostat Contro...

Страница 15: ...ing the heating operation Thermo ON and if the Water outlet temperature is 3 degree C higher than inlet water temperature pump tap L will change to HH In the cooling operation thermo ON always selected pump tap HH When only internal heater is ON pump tap HH or H will be selected Mode Thermo ON Just after starting Thermo ON in stability Thermo OFF Cooling HH HH LL Heating L HH LL Tank L HH STOP 9 F...

Страница 16: ...eater ON condition for Tank mode operation It has passed 30 minutes of Thermo ON Heat pump operation priority Water outlet temperature 43 C 11 Sterilization Mode Purpose To sterilize the water tank by setting the Temperature for sterilization 55 C Control starts condition Tank connection menu is set to YES on the control panel Sterilization menu is set to YES on the control panel Sterilization sig...

Страница 17: ... heat mode When outdoor unit under defrost control When test run for water circuit Valve type 0 NO type 1 NC type default Valve State OPEN CLOSE OPEN CLOSE Contact 15 16 No contact contact contact No contact Terminal board Nos 15 16 Example 12 2 Way Valve Control Optional Indoor Unit 15 16 2 WAY VALVE No voltage a contact static output Allowable contact voltage and Current 250VAC 2A SM830243 00_欧州...

Страница 18: ...g Code no DN 54 Data 00 Disconnected default 01 Operation signal interlocking 02 Internal Water Pump interlocking Installation manual undescribed During outputting the external pump the icon will be displayed on the remote controller Terminal board Nos 13 14 Example 13 External Water Pump Optional Indoor Unit 13 14 EXTERNAL WATER PUMP No voltage a contact static output Allowable contact voltage an...

Страница 19: ...nal Nos 17 18 If the setting is changed to 01 or 02 a signal will be output when the heat pump capacity is insufficient Signal output condition a and b and c and d and e a Tank mode b Water outlet temperature Setting water temperature 5 C c Water outlet temperature ON OFF timing of external device d After 20 minutes from previous External device OFF e Thermo ON 14 External Device Ready Demand Sign...

Страница 20: ...if nothing is connected If the contact is opened continuously for 60 seconds the icon is displayed on the remote controller In this condition External Device Ready Demand is not output but the Air to Water module can operate continuously Terminal board Nos 10 11 Indoor Unit 11 12 24VDC or AC 10 EXTERNAL DEVICE NOTICE Static input Allowable contact voltage and Current 24VDC or AC 6mA SM830243 00_欧州...

Страница 21: ...et outlet temperature 6 C After 5 minutes from previous water pump OFF The Test run for water circuit is performed After water pump ON for 4 minutes Water outlet temp less than 28 C more than 28 C Water inlet temp less than 8 C between 8 C and 20 C more than 20 C Outdoor temp 4 C over Antifreeze control complete Water Pump and Heater OFF Between 5 C and 4 C less than 5 C or sensor error or tempera...

Страница 22: ...door unit Indoor unit PCB failure or malfunction Check Check the power of the outdoor units and check communication wiring Alarm code F01 Alarm meaning Abnormal refrigerant sensor 1 E1 Alarm conditions A D step is 10 steps or less short circuit A D step is 1014 steps or more open circuit Possible Cause Faulty connector connection Faulty sensor Faulty indoor unit PCB Check Measure the sensor resist...

Страница 23: ...p is 1014 steps or more open circuit Possible Cause Faulty connector connection Faulty sensor Faulty indoor unit PCB Check Measure the sensor resistance Check that the sensor is operating normally Use a remote controller monitor or PC monitor to check the temperature that is recognized by the microcomputer Alarm code F11 Alarm meaning Abnormal water outlet sensor 2 BL Alarm conditions A D step is ...

Страница 24: ...nected Possible Cause Unmatched remote controller is connected Check Check the remote controller CZ RTC5 or after version is corresponding Alarm code P07 Alarm meaning Abnormal Internal heater overload Alarm conditions Overload protector of internal heater is active Possible Cause Faulty power supply connector connection Faulty connector connection Faulty overload protector of internal heater OLP ...

Страница 25: ... water flow switch Water leak in system Faulty connector connection Faulty water pump Faulty indoor unit PCB main Check Check the probable cause above If external pump runs though internal pump is off stop the external pump Be sure to synchronize external pump with internal pump Alarm code P12 Alarm meaning Abnormal water pump speed Alarm conditions Cannot detect rotation of pump motor Possible Ca...

Страница 26: ...xternal Device Notice is input Air to Water module can operate continuously Possible Cause Signal of External Device Notice is input Check Check the external device Other check points Even though set temperature is 45 C or more the water temperature does exceed 45 C or more There is the possibility that the internal heater has not worked properly Check below items Disconnection of heater Measure t...

Страница 27: ...3 1 Air to Water Indoor Unit 3 3 OUTDOOR UNIT REPAIR PROCEDURES Refer to the Service Manual of Outdoor Unit SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 15 14 13 48 ...

Страница 28: ... MEMO 3 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 14 13 48 ...

Страница 29: ...4 1 Air to Water Indoor Unit 4 4 OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER Refer to the Service Manual of Outdoor Unit SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 15 14 14 40 ...

Страница 30: ... MEMO 4 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 14 14 40 ...

Страница 31: ...LER FUNCTIONS 1 Simple Settings Function 5 2 2 Detailed Settings Function 5 4 3 Detailed Settings Function for Air to Water 5 7 4 Remote Controller Servicing Functions 5 10 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 16 10 47 54 ...

Страница 32: ...t run Sel Page Confirm 20 30 THU Maintenance func 5 Sensor info 6 Servicing check 8 Detailed settings Sel Page Confirm 20 30 THU 7 Simple settings Simple settings Unit no Code no Set data 01 3 1 0001 Sel Next 20 30 THU 3 Select the Code no by pressing the or button Change the Code no by pressing the or button Simple settings Unit no Code no Set data 1 0 0 0 1 3 Sel Next 20 30 THU 01 Confirm 4 Sele...

Страница 33: ... address 3 0064 Central control address 64 0099 No central control address set Setting at shipment NOTE Do not change any setting data that does not appear in this list Simple setting items Item code Item Description 03 Central control address Set when using a central control device Used when setting the central control address manually from the remote controller SM830243 00_欧州向け Air to Water S 80...

Страница 34: ...firm 20 30 THU 7 Simple settings Detailed settings Unit no Code no Set data 10 3 1 0001 Sel Next 20 30 THU 3 Select the Code no by pressing the or button Change the Code no by pressing the or button or keeping it pressed 4 Select the Set data by pressing the or button Select one of the Set data by pressing the or button Then press the button 5 Select the Unit no by pressing the or button and press...

Страница 35: ...address 14 10 11 12 13 0000 Function disabled 0001 Stops automatically 5 minutes after operation starts 0002 Stops automatically 10 minutes after operation starts 0123 Stops automatically 615 minutes after operation starts 0124 Stops automatically 620 minutes after operation starts Automatic stop time after operation start 0125 Stops automatically 625 minutes after operation starts 0030 0016 125 T...

Страница 36: ...er operation start The time at which an indoor unit is automatically stopped after operation starts can be set in increments of 5 minutes 35 OFF reminder function for weekly timer This setting switches the operation when the weekly timer is connected to the remote controller This can be used to prevent cases in which the unit is accidentally left ON There is no change when this setting is ON howev...

Страница 37: ...ttings for Air to Water START 20 30 THU Maintenance func 0 ECONAVI info 1 Outdoor unit error data 2 Service contact 3 RC setting mode Sel Page Confirm 20 30 THU Maintenance func 10 Set elec consumption 11 Set touch key 12 Check touch key Sel Page Confirm 20 30 THU 13 Air to Water unit Air to Water unit Air purge Pump speed setup Cancel int heater alarm Sel Set 20 30 THU Air to Water settings Air t...

Страница 38: ...termination temperature When Pump ON 0070 70 C 0071 71 C 0084 84 C 0085 85 C 28 Internal heater OLP determination temperature When Pump OFF 0070 70 C 0071 71 C 0084 84 C 0085 85 C 31 Temperature for sterilization 0050 50 C 0051 51 C 0055 55 C 0065 65 C 50 Thermo ON margin 0000 0 C 0001 1 C 0004 4 C 0005 5 C 51 Thermo OFF margin 004 4 C 003 3 C 002 2 C 001 1 C 0000 0 C 52 ON OFF timing of external ...

Страница 39: ...rol Upper limit 0025 25 C 0026 26 C 0044 44 C 0045 45 C 63 Lower limit 0025 25 C 0026 26 C 0044 44 C 0045 45 C 64 Cool mode setting range for Room temperature control Upper limit 0005 5 C 0006 6 C 0030 30 C 0045 45 C 65 Lower limit 0005 5 C 0006 6 C 0018 18 C 0045 45 C 66 Heat mode setting range for Room temperature control Upper limit 0005 5 C 0006 6 C 0030 30 C 0045 45 C 67 Lower limit 0005 5 C ...

Страница 40: ...run Operation with forced thermostat ON 4 Test run Press the button Sensor temperature display Temperature display from each sensor 5 Sensor info Servicing check display Alarm history display 6 Service check Simple settings Filter lifetime operating mode priority central control address and other settings 7 Simple settings Press the button Restart When settings are made from a remote controller th...

Страница 41: ...display from OFF to ON by pressing the or button Then press the button 3 Press the button TEST will be displayed on the LCD display 4 Press the button Test run will be started Test run setting mode screen appears on the LCD display Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Maintenance func 1 Outdoor unit error data 2 Servic...

Страница 42: ...age Confirm 20 30 THU 7 Simple settings Sensor info Unit no Code no Data Sel Next 20 30 THU 01 02 00 0028 0026 0026 1 1 Sensor info Unit no Code no Data Scroll 20 30 THU 01 02 00 0028 0026 0026 1 1 Sensor info Unit no Code no Data Scroll 20 30 THU 01 02 00 0028 0026 0026 1 1 Refer to the Service Manual of Outdoor Unit Outdoor unit sensors Indoor unit sensors Remote controller temp Indoor unit inta...

Страница 43: ...SIS Refer to the Service Manual of Outdoor Unit However Refer to page 5 12 operations in the high spec wired remote controller CZ RTC5 of Sensor temperature display function SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 15 14 15 37 ...

Страница 44: ... MEMO 6 2 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 2 2015 09 15 14 15 37 ...

Страница 45: ... Unit Air to Water Indoor Unit 7 TEST RUN from the remote controller CZ RTC5 1 Test Run 7 2 2 Auto Address Setting 7 3 3 Test Run for Water Circuit 7 4 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 17 9 42 54 ...

Страница 46: ...ed Test run setting mode screen appears on the LCD display Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Confirm Test run Change 20 30 THU Test run ON CZ RTC5 TEST START 20 30 THU TEST 20 30 THU COOL MODE SM83023...

Страница 47: ...r more seconds The Maintenance func screen appears on the LCD display 2 Press the or button to see each menu If you wish to see the next screen instantly press the or button Select 7 Simple settings on the LCD display and press the button The Simple settings screen appears on the LCD display Select the Unit no by pressing the or button for changes The indoor unit fan operates only at the selected ...

Страница 48: ...0 THU Purging air Air to Water unit Air purge Pump speed setup Cancel int heater alarm Air to Water settings Sel Set 20 30 THU Confirm Air to Water unit 20 30 THU Air purge failure failure success Air purge failure message is caused by abnormalities of following Reference of Alarm code P09 Abnormal water flow Reference of Alarm code P12 Abnormal Water Pump speed 1 2 you wish to see the next screen...

Страница 49: ...STATIC PRESSURE kpa WATERFLOW RATE L min P Q 1 2 3 4 5 6 7 NOT APPLICABLE RANGE NOT APPLICABLE RANGE Rated waterflow volume Type 125 Type 80 20 25 30 35 40 45 50 Pump speed Press the or button to see each menu If you wish to see the next screen instantly press the or button Select Pump speed setup on the LCD display and press the button The default setting is SPEED 3 Please ensure the minimum flow...

Страница 50: ...201509 SM830243 00_欧州向け Air to Water S 80MW1E5他 SM TRSM indb 1 2015 09 15 11 42 32 ...