48
AHU Kit – Installation Instructions –
11/2021
Installation
3. Loosen the 4 screws in the corners of the enclosure and remove the cover from the enclosure.
4.
Mount the backside of the enclosure to the wall or surface using field-supplied fixing screws
inserted through the previously prepared holes at each corner.
ATTENTION
Signal errors through noise from live power supply cords
Power supply cords can generate noise, which may cause signal errors, if they are run in close
proximity to any extra-low voltage control wiring.
►
Keep 230 V AC power supply wiring apart from the extra-low voltage control wiring for
sensors etc.
► Route 230 V AC power supply wiring through different cable glands than the extra-low
voltage control wiring.
5. Insert the wiring preferably from below the enclosure through the screwed cable glands and
connect the wires to each of the 6 connectors as required.
After having finished wiring and applying power to the AHU Kit, auto-addressing can be
performed and the parameters of the thermostat (advanced version only) can be set.
!
Содержание PAW-280PAH3M-1
Страница 2: ...Notes ...