8-1-5 RTEX synchronization and initialization error protection (Err. 84.3)
This alarm occurs when the initialization process fails to establish synchronization between the communication and
servo driver.
Cause
• The initialization process fails to synchronize the communication and servo
driver.
Detecting timing
• On power up of servo driver control power.
• Upon restarting by the reset command.
Internal process upon
detecting error
• Fails to establish RTEX communication (aborts due to incomplete initialization)
• RTEX communication status is still in INITIAL condition (transition).
Action
• Replace the servo driver if the cause is not removed after turning on control
power.
Alarm clear attribute
• Cannot be cleared.
Display on COM LED
• Lighting in red