No. SX-DSV02829 -
159-
7-3 Warning function
The warning will be triggered before the protective function is activated, and you can check the conditions such as
overload beforehand.
To clear the warning state, perform the same steps as for the normal clearing of alarms.
In addition, when an A-CLR input is in ON state, warning is always cleared.
This function does not support “Warning non-latch mode” that allows clearing of the error and transition to non-error
state in one second after the cause of the warning is eliminated.
Over-load warnings detected by using Over-load warning detection level (Pr6.73) or Over-load warning release level
(Pr6.74) are cleared when the load factor becomes lower than the level appropriate to clearing of the warning. The
warning latch function is not supported.
(1) Parameters
Class No.
At-
trib-
ute
*1)
Title
Range
Unit
Function
4
40
A
Selection of
Warning output 1
0–14
—
Select the type of warning issued as the warning output 1 (WARN1).
Setup value 0: ORed output of all warnings.
For 1 and subsequent see the table below.
4
41
A
Selection of
Warning output 2
0–14
—
Select the type of warning issued as the warning output 2.(WARN2)
Setup value 0: ORed output of all warnings.
For 1 and subsequent see the table below.
6
37
B
Oscillation
detecting level
0–1000
0.1%
Set up the oscillation detecting level.
Upon detection of a torque vibration whose level is higher than this setup
value, the oscillation detection alarm will be issued.
If set to 0, oscillation detection warning is disabled.
6
38
C
Warning mask
setting
-32768
–32767
—
Set the warning detection mask. To disable detection of a warning, place 1
to the corresponding bit.
6
73
A
Over-load warning
detection level
0–114
%
Set the threshold used to detect overload warnings during increase of
overload factor. Use overload factor for the threshold setting.
Setting 0 makes overload warnings detected with the existing condition
(85% of overload level).
Settings other than
“
Pr6.74
≦
Pr6.73 < (overload level)
”
also make
overload warnings detected with the existing condition (85% of overload
level).
6
74
A
Over-load warning
release level
0–114
%
Set the threshold used to clear active overload warnings during decrease of
overload factor. Use overload factor for the threshold setting.
Setting 0 makes overload warnings detected with the existing condition
(85% of overload level).
Settings other than
“
Pr6.74
≦
Pr6.73 < (overload level)
”
also make
overload warnings detected with the existing condition (85% of overload
level).
7
14
C
Main power OFF
warning detection
time
0
−
2000
1 ms
Specifies a time to wait until a main power off warning is detected when
main power shut-off continues.
TREX communication status AC_OFF becomes 1 when main power off is
detected.
0
−
9, 2000: Warning detection is disabled.
10
−
1999: Unit is [ms] • Setting resolution is 2 ms.
*1) For parameter attribute, refer to Section 9-1.
R1.00
Motor Business Unit, Panasonic Corporation