KW1M-H Eco-POWER METER
11
Recommended Cable
Use the transmission cables shown below for Eco-POWER METER RS485 communication system.
Cable
Conductor
Insulator
Cable
diameter
Applicable cable
Size
Resistance
(at 20
℃)
Material
Thickness
Twisted-
pair
with shield
1.25 mm
2
(AWG16)
or more
Max.16.8
Ω
/km
Polyethylene
Max.
0.5 mm
Approx.
8.5 mm
HITACHI
KPEV-S
1.25 mm
2
×
1P
Belden Inc. 9860
0.5 mm
2
(AWG20)
or more
Max.33.4
Ω
/km
Polyethylene
Max.
0.5 mm
Approx.
7.8 mm
HITACHI
KPEV-S
0.5 mm
2
×
1P
Belden Inc. 9207
VCTF
0.75 mm
2
(AWG18)
or more
Max.25.1
Ω
/km
PVC
Max.
0.6 mm
Approx.
6.6 mm
VCTF
0.75 mm
2
×
2C
(JIS)
Cable
Section
Notes
1) Use shielded type twist cables.
2) Use only one type of the transmission cables.
2) Do not mix different types of the cables.
3) Use twist pair cables under a bad noise
environment.
Twisted-pair
with shield
VCTF
3.7 Low Voltage Directive
When using in the application confirming to EN61010-1/IEC61010-1, make sure to satisfy the following
conditions.
(1) Pulse output part secure only basic insulation. In order to secure reinforced (double) insulation
demanded by EN 61010-1/ IEC61010-1, secure basic insulation or more with load side and
reinforced (double) insulation with communication system side.
(2) Provide the voltage input part with an EN60947-1 or EN60947-3 compliant circuit breaker.
The breaker that connects to the voltage input part must arrange at the position easily reached,
and display shows it is the breaker of the equipment.
(3) Use a wire with basic insulation or more for a wire cramped (or connected) CT.
【
Environmental conditions
】
・
Overvoltage category
Ⅱ
, Pollution degree
2
・
Indoor use
・
An ambient temperature of –10 to 50
℃
・
An ambient non-condensing humidity of 35 to 85%RH (at 20
℃
)
・
Altitude of 2000m or less
【
Mount the product in a place with
】
・
A minimum of dust, and an absence of corrosive gases
・
No flammable, explosive gasses
・
Few mechanical vibrations or shocks
・
No exposure to direct sunlight
・
No large capacity electromagnetic switches or cables through which large current is flowing
Conductor Insulator
Jacket
Shield
Jacket
Conductor Insulator