FUNCTION SETTINGS
© Panasonic Industrial Devices SUNX Co., Ltd. 2019
5-13
5-2-3 Hysteresis (
)
If the judgment value fluctuates near the HIGH or LOW set value, the judgment output may re
-
peat ON / OFF and operation may become unstable. Operation can be stabilized by increasing
the hysteresis value.
●
When the hysteresis is "0"
Fluctuation of the judgment value (JUDGE.V) near the HIGH set value (or LOW set value)
will cause the judgment output to become unstable.
HIGH set value
LOW set value
HIGH
GO
LOW
Judgment value
Not stable
Fluctuates near HIGH set value or LOW set value
●
When a hysteresis is set
By setting a hysteresis, the judgment output will remain stable even if the judgment value
(JUDGE.V) fluctuates near the HIGH set value (or LOW set value).
Hysteresis
Hysteresis
Stable
HIGH set value
LOW set value
HIGH
GO
LOW
Judgment value
Fluctuates near HIGH set value or LOW set value