Panasonic FP-PS24-050E Скачать руководство пользователя страница 1

FP0 Series
Programmable Controller

Panasonic ... the new name for

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]

Содержание FP-PS24-050E

Страница 1: ...FP0 Series Programmable Controller Panasonic the new name for CTi Automation Phone 800 894 0412 Fax 208 368 0415 Web www ctiautomation net Email info ctiautomation net ...

Страница 2: ...ed to I O 32 points control unit Choose among 3 types of attachment DIN rail Slim attachment plate model Flat attachment plate model cannot be used with expansions Input output terminal TOOL Port Hooks up by using the programming software or FPWIN GR and a single cable 25mm 90mm The photo shows an I O 14 point control unit This size is uniform for all except the I O 32 point control unit Supply vo...

Страница 3: ...control Parts feeders Food processing and packaging machines Parking meters Auto stockers Driving range Easy Expansion up to 128 I Os Control unit Expansion unit Expansion unit Expansion unit Maximum possible expansion is three units Control unit Expansion unit Expansion unit Expansion unit 105mm The photo illustrates adding three I O 32 point expansion units to an I O 32 point control unit yieldi...

Страница 4: ...this event the maximum number of I O points when using a relay output type control panel is 110 10 points Input 6 points FP0 C10RSA FP0 C10CRSA with 2nd RS232C FP0 C14CRSA with 2nd RS232C FP0 C16PA PNP FP0 C16TA NPN FP0 C32PA PNP FP0 C32TA NPN FP0 C16CPA PNP FP0 C16CTA NPN with 2nd RS232C FP0 C32CPA PNP FP0 C32CTA NPN with 2nd RS232C FP0 C14RSA Output 4 points 10 points Input 6 points Output 4 poi...

Страница 5: ...put type Analogue I O Units Thermocouple and RTD Units Networking Units PROFIBUS FP0 DPS2 DP Slave MEWNET F FP0 IOL MEWNET F Slave S Link CPU FP0 SL1 S LINK Master FP0 E16RSA FP0 E8XA FP0 E16XA FP0 E8RSA FP0 E8YRSA 8 points Input 8 points 16 points Input 16 points 8 points Input 4 points Option Output 8 points Output 4 points 16 points Input 8 points Output 8 points FP0 E8YPA PNP FP0 E8YTA NPN FP0...

Страница 6: ...P0 I O refresh Program execution I O refresh Program execution Sensor input signal Cannot read Lengthening of sensor input signal Can read With pulse catch function Internal processing in the FP0 I O refresh Program execution I O refresh Program execution Interrupt program Interrupt input Interrupt program executed when interrupt input enters A top class large 5k and 10k steps program capacity hou...

Страница 7: ...lade control signal Encoder output inputted into high speed counter Serial communication function The FP0 s second RS232C port types C10CRS C14CRS C16C C32C and T32C allows direct connection to computers and operation display panels Also bi directional data communication with barcode readers and other RS232C devices is made easy Both the relay type and transistor output type control units are opti...

Страница 8: ... FP0 C14CRS FP0 C16C FP0 C32C and FP0 T32C offers flexible programming i e General Purpose In this configuration it is possible to realise communication connections with different RS232C peripheral devices e g Bar Code Readers slave devices printers measurement sensors or telecommunication transmitters etc Communication Interface COM Port Freely programmable RS232C interface for CPU modules type F...

Страница 9: ...ct body Input output status can be verified at a glance Terminal type can be plugged straight in without resorting to crimping made by Phoenix Contact Co Can handle wires from 0 3 to 1 25mm2 Compatible models FP0 C10RS C10CRS C14CRS E8RS E16RS Unit connectors can be used with 16 points and 32 points units Due to the loose wiring pressure contact type design wiring is easy without the need for insu...

Страница 10: ...93 75 187 5 500 1 500 3 000 6 000 12 000 Kbaud automatic baud rate detection Range of adresses that can be set 0 125 PROFIBUS connection Configuration 9 pin D sub connector 2 words input 2 words output up to 6 words input 6 words output if no other expansion is connected Remote I O max 3 FP0 expansion units FP0 communication Via FP0 system bus Power supply 24VDC 21 6VDC 26 4VDC Max power consumpti...

Страница 11: ...t time filtering Clock Calendar function Available Available Not available None Other Built in Functions Item Description Number of I O points Expansion S LINK block 64 input points 64 output points fixed Max 3 units Expansion section Max 96 points Operation speed 0 9µs step Internal memory EEPROM Memory capacity 5k steps Memory Internal relay of Timer Counter execution Data register 1 008 points ...

Страница 12: ...s Number of control I O points per an I O link unit 64 points Input 32 points and Output 32 points Remote I O map allocation Interface Transmission error check 32X 32Y Conforms to RS485 CRC Cyclic Redundancy Check method FP0 IOL Link Unit Specifications By using C NET you can use multiple FP0s as data collection terminals By using the C NET network and exclusive adapters you can connect multiple F...

Страница 13: ...ision temperature control at low cost 13 Temperature control FP0 TC8 8 channels FP0 TC4 4 channels Item Specification Input points Input range Up to 8 channels per unit The number of input points can be changed 2 4 6 and 8 channels are available Thermocouple types K J 100 C to 500 C Thermocouple types T 100 C to 400 C Thermocouple types R 0 C to 1500 C Resolution 0 1 C Sampling cycle 300ms when us...

Страница 14: ...es to factory production systems Each CPU supports up to 3 FP0 analogue units Combination with digital and analogue expansion units is freely allowed Highest performance is offered with 12 bit resolution With a current and voltage output conversion time of up to 500µs the units are capable of high speed processing The multimode FP0 analogue unit can be configured via the DIP switches on the front ...

Страница 15: ...terminal temperature selectable J up to 750 C or 100 C to terminal temperature selectable T up to 350 C or 100 C to terminal temperature selectable 0 to 5V 0 to 20mA K 0 to K 4000 H 0000 to H 0FA0 1 10 to 10V 100 to 100mV K 2000 to K 2000 HF830 to H07D0 Thermocouple The value of broken wire detection is K 20000 For plus K temperature of terminal 2 to K 1000 Unit is Celsius For minus K 100 to K tem...

Страница 16: ...ntrolled electrical installations The library includes linear and non linear controller types such as the P I PI PID controller and two points three points controller with and without hysteresis Programmable logic arrays for dead band interpolation lamp limiting dead time and averaging are also in cluded Item Specification Input points Input type Up to 6 channels per unit 3 inputs per one Phoenix ...

Страница 17: ...ol relay MCR 32 points Number of labels JMP and LOOP 64 labels 255 labels Differential points Unlimited number of points Number of step ladder 128 stages 704 stages Number of subroutines 16 subroutines 100 subroutines Special functions High speed counter 1 phase 4 points 10kHz in total or 2 phases 2 points 2kHz in total Not available Pulse output Not available 2 points 10 kHz in total enable to co...

Страница 18: ... input voltage 24VDC Operating voltage range 21 6 to 26 4VDC Rated input current 4 3mA or less at 24VDC Input points per common 6 points common C10RS 8 points common C14RS C16T C16P E16T E16P 16 points common C32T C32P E32T E32P ON voltage ON current 19 2V or less 3mA or less OFF voltage OFF current 2 4V or more 1mA or more Input impedance Approx 5 6kΩ Response time OFF ON 50µs or less at X0 X1 10...

Страница 19: ...ib Fewer errors through defined data types and encapsulation Well structured through programme organisation units task and project management Online monitoring and diagnostic Ethernet and Modem communication for remote programming service and diagnostic Password protection with different levels Many additional application libraries available IEC 61131 3 protects your investments for the future Con...

Страница 20: ...on on site a mouse is not required for input search write monitor and timer edit operations Everything can be accomplished with a keyboard alone 2 Standard Windows operations such as copy and paste are included 3 Supports all FP series machines Software created with NPST GR Ver 3 or 4 can also be used 4 Inherits convenient functions developed for NPST GR Features OS Required hard disc capacity Rec...

Страница 21: ... off status and register values and perform calculations based on register values Excel macros are not necessary PCWAY The connection between PLC and SCADA software Provides a standard interface between our FP Series PLCs and various SCADA HMI software used to build a monitoring system compliant with commercially available OPC clients It is also possible to use OPC automation interface to link our...

Страница 22: ... number FP0 C32PA PNP FP0 C32TA NPN PNP NPN output type Order number FP0 C32CPA PNP FP0 T32CPA PNP 10K FP0 C32CTA NPN FP0 T32CTA NPN 10K with 2nd RS232C interface Terminal type Order number FP0 C14RSA Output 4 points 10 points Input 6 points Output 4 points 14 points Input 8 points Output 6 points 14 points Input 8 points Output 6 points 16 points Input 8 points Output 8 points 16 points Input 8 p...

Страница 23: ...t 24VDC 2 1A PROFIBUS PROFIBUS DP Slave or Remote I O Order number FP0 DPS2 MEWNET F MEWNET F Slave Order number FP0 IOL S LINK CPU S LINK Master Order number FP0 SL1 Order number AFP1114V2 Networking units Analogue units AC power supply FP Memory Loader Handy Programmer Read or write programs from or to a PLC Order number AFP8670 4 points Input 4 points Terminal type Order number FP0 TC4 Terminal...

Страница 24: ...puter With 30cm dedicated cable Power source unnecessary Order number AFP15402 DIN rail Standard DIN rail of width 35mm 1 378inch and length 1m Order number Stopper fitting DIN rail stopper fitting ATA4806 Order number AFP0521 Order number AFP0523 Accessories Products and order numbers Notes 1 One I O cable set 2 cables is necessary with the following models FP0 C10RS C14RS E8RS E16RS 2 One I O ca...

Страница 25: ...ware USB port dongle Control CommX Order number AFW20011 Software Printer port dongle AFW20031 Software USB port dongle MEWTOCOL OPC Server Order number AFPS01510 1 license AFPS01515 5 licenses AFPS01516 10 licenses Type of unit Part number Current Consumption Supply to the power supply connector of the control unit 1 Supply to the power supply connector of the expansion and intelligent units 2 Co...

Страница 26: ...e Shock resistance Life time min Mounting Size Input connection AC side Output connection DC side Status display 0 C to 55 C 20 C to 70 C 5 to 95 non condensing 5 to 95 non condensing 10 to 55Hz 1 cycle min double amplitude of 0 75mm 10 min on 3 axes 10g min 4 times on 3 axes 7 years at nom load 25 C ambient temperature 20000 h at 55 C with full load continuous operation DIN rail or FP0 flat attac...

Страница 27: ...utput FP0 A21A FP0 A80 8 analogue inputs FP0 A80A FP0 TC4 4 thermocouple inputs FP0 TC4 FP0 TC8 8 thermocouple inputs FP0 TC8 FP0 RTD6 6 RTD Inputs Pt 100 Pt 1000 Ni 1000 FP0 RTD6 3 AC Power Supply Product Name Part Number FP0 AC Power Supply 24VDC 0 7A FP0 PSA2 4 Network Product Name Part Number FP0 DPS2 PROFIBUS DP Slave or Remote I O unit FP0 DPS2 FP0 IOL MEWNET F Slave unit I O link FP0 IOL FP...